Research on uhv transmission nears completion of single-phase testing at 1000 to 1500 kV
Journal Article
·
· EEI (Edison Elec. Inst.) Bull., v. 41, no. 4, pp. 190-192
OSTI ID:4330563
Bundles of 4, 6, 8, 10, and 12 conductors were tested, using a single- phase overhead test line energized by means of a singlephase bus, which includes a 1500-Kv single-phase 33-Mva autotransformer, a lighthing arrester, a precision SF/sub 6/-insulated capacity, and a coupling capacitor for radio-noise measurements. The test line was energized in March 1970 and was used to determine corona performance of many different bundle conductors. Audible noise, radio noise, and corona loss were measured under varying weather conditions. Two test cages were used for investigations of audible noise, radio noise, corona loss for different conductor bundle configurations, and conductor bundles for voltages up to 1500 Kv. Proposals are made for line performance measurements on a three-phase basis from 1974 to 1976. (MCW)
- Research Organization:
- Originating Research Org. not identified
- NSA Number:
- NSA-29-028818
- OSTI ID:
- 4330563
- Journal Information:
- EEI (Edison Elec. Inst.) Bull., v. 41, no. 4, pp. 190-192, Journal Name: EEI (Edison Elec. Inst.) Bull., v. 41, no. 4, pp. 190-192; ISSN BEEIA
- Country of Publication:
- Country unknown/Code not available
- Language:
- English
Similar Records
Three-phase UHV AC transmission research, 1977-1979. [1000 and 1500 kV]
Investigation of the corona performance of conductor bundles for 800-kV transmission
KEPCO 765 kV transmission system development corona and electric field effects studies
Technical Report
·
Fri May 01 00:00:00 EDT 1981
·
OSTI ID:6513824
Investigation of the corona performance of conductor bundles for 800-kV transmission
Conference
·
Tue Dec 31 23:00:00 EST 1974
· IEEE Trans. Power Appar. Syst.; (United States)
·
OSTI ID:7295343
KEPCO 765 kV transmission system development corona and electric field effects studies
Conference
·
Sat Dec 30 23:00:00 EST 1995
·
OSTI ID:433830