Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Guam Power Authority automatic underfrequency load shedding study

Conference ·
OSTI ID:433800
 [1]; ; ;  [2]
  1. Hawaiian Electric Co., Honolulu, HI (United States)
  2. Guam Power Authority, Agana (Guam)

This paper describes the development of a new automatic underfrequency load shedding scheme on the Guam Power Authority`s (GPA) system using a transient stability simulation program. The new scheme strives to minimize the amount of load shed by selecting frequency settings based on the severity of generation or load unbalance and the availability of spinning reserves. The fast speed of frequency decay due to loss of generation is shown to be particularly pronounced in an island system, requiring more careful design of any load shedding scheme than large interconnected systems. The use of a well-prepared transient stability study model allows the simulation of specific contingencies and the fine-tuning of load shedding strategies for optimality. The trade-off between equipment protection, customer service availability, and practical operating issues, such as, synchronization of generators to the grid, are discussed.

OSTI ID:
433800
Report Number(s):
CONF-951136--; ISBN 0-7803-2981-3
Country of Publication:
United States
Language:
English

Similar Records

Underfrequency load shedding
Technical Report · Mon Feb 28 23:00:00 EST 1983 · OSTI ID:7142082

Electrical transient stability and underfrequency load shedding analysis for a large pump station
Journal Article · Tue Dec 31 23:00:00 EST 1996 · IEEE Transactions on Industry Applications · OSTI ID:479396

Electrical transient stability and underfrequency load shedding analysis for a large pump station
Conference · Sat Dec 30 23:00:00 EST 1995 · OSTI ID:392610