Electrical transients from faults, loss of generation, and load swings can disrupt pump station operations. Isolated stations with no utility tie and those with weak utility ties are especially at risk. Relative to this problem, the following four main issues are addressed: (1) Analyze the methods that use high-speed underfrequency load shedding to maintain system stability and preserve station operations. (2) Analyze combustion gas turbine generator and diesel generator transient responses, as they pertain to the Electrical Engineer. (3) Discuss system component modeling and the use of low voltage circuit switching devices to shed loads. (4) Compare two computer analysis program outputs for underfrequency load shedding responses.