PROCEDURE FOR MEASURING FREON 114 LEAK RATES IN CASCADE COOLANT CONDENSERS BY THE GAS DILUTION METHOD
Technical Report
·
OSTI ID:4303433
The gas dilution method for the measurement of Freon leak rates to the water side of cascade coolant condensers has been tested on various condensers in the X-333 building and on one condenser in the X-330 building. The gas dilution method involves injecting Freon 115 (CClF/sub 2/--CF/sub 3/) into the water inlet of a condenser suspected of leaking Freon 114 (mixture of CClF/sub 2/-CClF/sub 2/ and CCl/sub 2/F--CF/sub 3/). It is assumed tht the two gases mix uniformly in the condenser before a gas sample is withdrnwn from the three-way vent line valve. Knowing the rate of Freon 115 infection, and measuring the ratio of freon 114 to Freon 115 in the outlet gag sample by an infrared method to be described, the Freon 114 leak rate can be calculated accurately. (auth)
- Research Organization:
- Goodyear Atomic Corp., Portsmouth, Ohio
- DOE Contract Number:
- AT-(33-2)-1
- NSA Number:
- NSA-12-015472
- OSTI ID:
- 4303433
- Report Number(s):
- GAT-T-547
- Country of Publication:
- United States
- Language:
- English
Similar Records
REACTIONS OF FREON-114 WITH FLUORINE
Stratospheric photodissociation of several saturated perhalo chlorofluorocarbon compounds in current technological use (fluorocarbons-13, -113, -114, and -115)
THE EFFECT OF FREON-114 ON SPACE RECORDERS
Technical Report
·
Wed May 14 00:00:00 EDT 1958
·
OSTI ID:4314941
Stratospheric photodissociation of several saturated perhalo chlorofluorocarbon compounds in current technological use (fluorocarbons-13, -113, -114, and -115)
Journal Article
·
Wed Jan 11 19:00:00 EST 1978
· J. Phys. Chem.; (United States)
·
OSTI ID:5307379
THE EFFECT OF FREON-114 ON SPACE RECORDERS
Technical Report
·
Fri Apr 24 23:00:00 EST 1959
·
OSTI ID:4206829