Harmonic overvoltages in industrial power system with capacitors and saturated transformers

Conference ·
OSTI ID:427915
;  [1]; ;  [2]
  1. Inst. National Polytechnique de Grenoble, Saint Martin D`Heres (France). Lab. d`Electrotechnique
  2. Electricite de France, Clamart (France). Direction des Etudes et Recherches
This paper presents a new method for determination of instantaneous saturation and hysteresis loops of transformers with a sinusoidal or nonsinusoidal voltage excitation by taking into account only the rms values and no-load losses. This model is used to study harmonic overvoltages in an industrial power system with saturated transformers and power factor correction capacitors. Influences of short-circuit power source and switching orders of transformer and capacitor on overvoltages are investigated.