A model of suspension clamp rocking action due to aeolian vibrations of overhead conductors

Book ·
OSTI ID:403386
;  [1]; ;  [2]
  1. Hydro-Quebec, Varennes, Quebec (Canada)
  2. Univ. Laval, Quebec (Canada)
Aeolian vibrations of overhead conductors may lead to wire fatigue failures in the vicinity of suspension clamps. This paper presents an analytical model of the clamp rocking action which takes into account conductor vibrations in adjacent spans, the moment of inertia of the suspension clamp and the transverse impedance of the insulator string. Traveling waves are used to represent conductor vibrations and conductor curvatures are calculated on both sides of the clamp. The results of a sensitivity analysis are presented to identify the most important parameters influencing conductor vibrations. The entire analysis is done at a single frequency of vibration and from a structural point of view only. Finally, calculated bending amplitudes are compared to experimental results.
OSTI ID:
403386
Report Number(s):
CONF-960706--; ISBN 0-7918-1775-X
Country of Publication:
United States
Language:
English

Similar Records

Influence of vibration recorders on conductor vibration
Journal Article · Thu Mar 31 23:00:00 EST 1994 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6985720

Aeolian vibration control of overhead electrical transmission line conductors
Book · Thu Nov 30 23:00:00 EST 1995 · OSTI ID:129015

Suspension clamp and ACSR electrical conductor contact conditions
Journal Article · Wed Mar 31 23:00:00 EST 1993 · Journal of Environmental Engineering (New York); (United States) · OSTI ID:6439539