Results of acoustic emission tests on Halon fire bottles

Conference ·
OSTI ID:402290

An acoustic emission tester for aircraft Halon bottles has been developed. The necessary load is applied by heating the bottles. Acoustic emission is monitored during the heating by six sensors held in position by a special fixture. This fixture was designed to fit spheres with diameters between 5 and 16 inches. A prototype has been undergoing testing in two commercial Halon bottle repair and test facilities. Results to date indicate that about 97 percent of the bottles tested show no indications of any flaws. The other three percent have had indications of flaws in non-critical areas of the bottles. All bottles tested to date have passed the hydrostatic test required by the Department of Transportation (DOT).

Research Organization:
Sandia National Labs., Albuquerque, NM (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States); Federal Aviation Administration, Washington, DC (United States)
DOE Contract Number:
AC04-94AL85000
OSTI ID:
402290
Report Number(s):
SAND--96-2305C; CONF-9610109--1; ON: DE96015192
Country of Publication:
United States
Language:
English