Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

DYNASTORE operating cost analysis of energy storage for a midwest utility

Conference ·
OSTI ID:391709
 [1];  [2]
  1. Missouri Univ., Rolla, MO (United States). Dept. of Electrical Engineering
  2. Sandia National Labs., Albuquerque, NM (United States)

The objective of this project was to determine the savings in utility operating costs that could be obtained by installing a Battery Energy Storage System (BESS). The target utility was Kansas City Power and Light (KCPL), a typical Midwestern utility with a mix of generating plants and many interconnections. The following applications of battery energy storage were modeled using an Electric Power Research Institute (EPRI) developed and supported program called DYNASTORE: (1) Spinning Reserve Only (2) Load Leveling with Spinning Reserve (3) Load Leveling Only (4) Frequency Control DYNASTORE commits energy storage units along with generating units and calculates operating costs with and without energy storage, so that savings can be estimated. Typical weeks of hourly load data are used to make up a yearly load profile. For this study, the BESS power ranged from ``small`` to 300 MW (greater than the spinning reserve requirement). BESS storage time ranged from 1 to 8 hours duration (to cover the time-width of most peaks). Savings in operating costs were calculated for each of many sizes of MW capacity and duration. Graphs were plotted to enable the reader to readily see what size of BESS affords the greatest savings in operating costs.

Research Organization:
Sandia National Labs., Albuquerque, NM (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC04-94AL85000
OSTI ID:
391709
Report Number(s):
SAND--96-2238C; CONF-9610165--1; ON: DE96015019
Country of Publication:
United States
Language:
English

Similar Records

Assessment of utility side cost savings from battery energy storage
Conference · Sat Jul 01 00:00:00 EDT 1995 · OSTI ID:125166

Assessment of utility side cost savings from battery energy storage
Journal Article · Fri Aug 01 00:00:00 EDT 1997 · IEEE Transactions on Power Systems · OSTI ID:538096

User's guide to DYNASTORE: A computer model for quantifying dynamic energy storage benefits
Technical Report · Fri Nov 30 23:00:00 EST 1990 · OSTI ID:6285270