Determination of locations and sizes for active power line conditioners to reduce harmonics in power systems
Journal Article
·
· IEEE Transactions on Power Delivery
- Chung Yuan Univ., Chung Li (Taiwan, Province of China). Dept. of Electrical Engineering
The APLC (Active Power Line Conditioner) is a type of active power filter that compensates the voltage waveform distortion caused by harmonics in power systems. This paper presents a new approach based on an optimization theory to investigate the determination of locations and sizes of APLCs. The objective is to minimize the new APLC injection currents and the voltage distortion while satisfying the harmonic standard. The test result for an 18-bus distribution system shows the applicability of the proposed method.
- OSTI ID:
- 372252
- Report Number(s):
- CONF-960111--
- Journal Information:
- IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 3 Vol. 11; ISSN 0885-8977; ISSN ITPDE5
- Country of Publication:
- United States
- Language:
- English
Similar Records
Harmonic distortion correction using active power line conditioners. Master`s thesis
Controlling harmonic voltage and voltage distortion in a power system with multiple active power line conditioners
Harmonic and power factor correction by means of active line conditioners with adaptive estimation control
Thesis/Dissertation
·
Thu Jun 01 00:00:00 EDT 1995
·
OSTI ID:218063
Controlling harmonic voltage and voltage distortion in a power system with multiple active power line conditioners
Journal Article
·
Sat Jul 01 00:00:00 EDT 1995
· IEEE Transactions on Power Delivery
·
OSTI ID:136605
Harmonic and power factor correction by means of active line conditioners with adaptive estimation control
Thesis/Dissertation
·
Mon Dec 31 23:00:00 EST 1990
·
OSTI ID:6030252