Estimation of steady-state unbalanced system conditions combining conventional power flow and fault analysis software
Conference
·
OSTI ID:367400
- Nordostschweizerische Kraftwerke AG, Baden (Switzerland)
- Swiss Federal Inst. of Tech., Zurich (Switzerland)
In real three-phase power systems the voltages and currents are not fully symmetrical. A method has been developed to estimate the effects of slight unbalanced network conditions for steady-state operation. A conventional power flow is followed by a linear incremental calculation using a three-phase model of the network. The unbalanced condition is handled like a multiple unbalanced fault. The process is illustrated for the case of a transformer bank with non-identical single phase units. The results show the effects of different transformer reactances and different voltage ratios, respectively.
- OSTI ID:
- 367400
- Report Number(s):
- CONF-950525--
- Country of Publication:
- United States
- Language:
- English