Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Estimation of steady-state unbalanced system conditions combining conventional power flow and fault analysis software

Journal Article · · IEEE Transactions on Power Systems
DOI:https://doi.org/10.1109/59.486128· OSTI ID:244777
;  [1];  [2]
  1. Nordostschweizerische Kraftwerke AG, Baden (Switzerland)
  2. Swiss Federal Inst. of Tech., Zurich (Switzerland)
In real three-phase power systems the voltages and currents are not fully symmetrical. A method has been developed to estimate the effects of slight unbalanced network conditions for steady-state operation. A conventional power flow is followed by a linear incremental calculation using a three-phase model of the network. The unbalanced condition is handled like a multiple unbalanced fault. The process is illustrated for the case of a transformer bank with non-identical single phase units. The results show the effects of different transformer reactances and different voltage ratios, respectively.
OSTI ID:
244777
Report Number(s):
CONF-950525--
Journal Information:
IEEE Transactions on Power Systems, Journal Name: IEEE Transactions on Power Systems Journal Issue: 1 Vol. 11; ISSN 0885-8950; ISSN ITPSEG
Country of Publication:
United States
Language:
English

Similar Records

Estimation of steady-state unbalanced system conditions combining conventional power flow and fault analysis software
Conference · Sat Dec 30 23:00:00 EST 1995 · OSTI ID:367400

Fault analysis of multi-phase unbalanced nonradial power distribution systems
Journal Article · Mon May 01 00:00:00 EDT 1995 · IEEE Transactions on Industry Applications · OSTI ID:55485

Analysis of simultaneous unbalanced faults, using three-port network theory
Conference · Fri Sep 01 00:00:00 EDT 1995 · OSTI ID:94243