Experience and field evaluation of a condition monitoring system for high-voltage circuit breakers - an update

Technical Report ·
OSTI ID:269644
This paper presents two case studies that detail the benefits of a condition - monitoring system installed on a 400-kV air-blast PK type circuit breaker and an 800-kV SFA SF{sub 6} double-pressure circuit breaker. On the air-blast breaker, the monitoring system detected a mechanical malfunction that was judged sufficiently severe to reduce the breaking capability of the breaker, and possibly cause a catastrophic explosion. In the case of the SFA breaker, a deficiency in the high-pressure tank insulation was found during the past winter when the outdoor temperature reached -25{degrees}F. The paper also briefly discusses the upgrading of the monitoring system since the last EPRI conference and its adaptation to other strategic equipment.
Research Organization:
Electric Power Research Inst., Palo Alto, CA (United States); Cambias and Associates, Covington, LA (United States)
OSTI ID:
269644
Report Number(s):
EPRI-TR--105838; CONF-9411304--
Country of Publication:
United States
Language:
English

Similar Records

Switching of extra high voltage circuits: design of air blast circuit breakers
Journal Article · Mon Nov 30 23:00:00 EST 1964 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6874358

Development of improved methods for type testing present day medium voltage circuit breakers for outdoor service
Journal Article · Thu Dec 31 23:00:00 EST 1992 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6502699

An on-line condition-monitoring system for high voltage SF{sub 6} circuit breakers
Technical Report · Thu Feb 29 23:00:00 EST 1996 · OSTI ID:269641