This paper presents the results on noise testing of a fan only, as well as the results of a steel silencer and of flexible silencers that were connected directly to a fan. On-site facilities and free-field method set by the British Standards Institution were used to measure and then compare the fan only and different practical silencer configuration setups. In order to determine the fan-silencer combination that would give the maximum noise attenuation, total noise intensity, noise contributed to by the fan motor only, as well as aerodynamical noise created through air interacting with the fan parts were considered to obtain decibel readings for the octave bands. Subsequently, the optimal configuration found was the setup with flexible silencers on the fan inlet and the fan outlet. If only one silencer is used, it should be installed on the fan inlet. The aerodynamic noise affects the low frequencies. The flow noise is then overtaken at 1 kHz by the mechanical noise.

OSTI ID:
269254
Report Number(s):
CONF-9506227--
Country of Publication:
United States
Language:
English

Similar Records

Noise-emission characteristics of circular mechanical, natural, and fan-assist natural-draft cooling towers with silencers
Conference · Fri Dec 31 23:00:00 EST 1976 · Proc. Am. Power Conf.; (United States) · OSTI ID:6661189

Installation effects in ducted fan systems
Book · Sat Dec 31 23:00:00 EST 1983 · OSTI ID:5803519

Fan noise reduction from a supersonic inlet during simulated aircraft approach
Journal Article · Fri Mar 31 23:00:00 EST 1995 · Journal of Engineering for Gas Turbines and Power · OSTI ID:78170