Passive Islanding Detection of Inverter-Based Resources in a Noisy Environment (in EN)

Journal Article · · Energies
DOI:https://doi.org/10.3390/en17174405· OSTI ID:2582964

Islanding occurs when a load is energized solely by local generators and can result in frequency and voltage instability, changes in current, and poor power quality. Poor power quality can interrupt industrial operations, damage sensitive electrical equipment, and induce outages upon the resynchronization of the island with the grid. This study proposes an islanding detection method employing a Duffing oscillator to analyze voltage fluctuations at the point of common coupling (PCC) under a high-noise environment. Unlike existing methods, which overlook the noise effect, this paper mitigates noise impact on islanding detection. Power system noise in PCC measurements arises from switching transients, harmonics, grounding issues, voltage sags and swells, electromagnetic interference, and power quality issues that affect islanding detection. Transient events like lightning-induced traveling waves to the PCC can also introduce noise levels exceeding the voltage amplitude by more than seven times, thus disturbing conventional detection techniques. The noise interferes with measurements and increases the nondetection zone (NDZ), causing failed or delayed islanding detection. The Duffing oscillator nonlinear dynamics enable detection capabilities at a high noise level. The proposed method is designed to detect the PCC voltage fluctuations based on the IEEE standard 1547 through the Duffing oscillator. For the voltages beyond the threshold, the Duffing oscillator phase trajectory changes from periodic to chaotic mode and sends an islanded operation command to the inverter. The proposed islanding detection method distinguishes switching transients and faults from an islanded operation. Experimental validation of the method is conducted using a 3.6 kW PV setup.

Research Organization:
National Renewable Energy Laboratory (NREL), Golden, CO (United States)
Sponsoring Organization:
USDOE
Grant/Contract Number:
AC36-08GO28308
OSTI ID:
2582964
Journal Information:
Energies, Journal Name: Energies Journal Issue: 17 Vol. 17; ISSN 1996-1073; ISSN ENERGA
Publisher:
MDPICopyright Statement
Country of Publication:
United States
Language:
EN

Similar Records

Analysis and performance assessment of the active frequency drift method of islanding prevention
Journal Article · Wed Sep 01 00:00:00 EDT 1999 · IEEE Transactions on Energy Conversion (Institute of Electrical and Electronics Engineers) · OSTI ID:20001194

A Data-Driven Passive Islanding Detection Scheme
Journal Article · Thu Dec 28 23:00:00 EST 2023 · IEEE Transactions on Industry Applications · OSTI ID:2447847

A Data-Driven Passive Islanding Detection Scheme
Conference · Sun Feb 19 23:00:00 EST 2023 · OSTI ID:1963928

Related Subjects