Pool Boiling Reliability Tests and Degradation Mechanisms of Microporous Copper Inverse Opal (CuIOs) Structures
The rising power density in electronic systems requires thermal management solutions that are both high-performing and reliable. Porous materials such as Copper Inverse Opal (CuIOs) have unique structural features, including high permeability and high thermal conductivity, to enhance pool boiling performance. However, there is little understanding of the degradation mechanism of such porous materials under pool boiling conditions. In this study, samples of 10 ..mu..m thick CuIOs with 4.8 ..mu..m diameter, covering silicon substrate of area 11 mm x 11 mm, with various heated areas ranging from 2.5 mm x 2.5 mm to 10 mm x 10 mm, were tested in 100 degrees C deionized water at a constant heat flux of 110 Wcm -2 for 3-to-7 days. The combined effect of erosion and corrosion caused structural degradation of the CuIOs. The directly heated area had the most severe degradation while the edge of the heater and the unheated area showed progressively less degradation, maintaining some CuIOs structure even after the 7-day reliability test. Among all the tested samples with various heater sizes, the 2.5 mm x 2.5 mm heater sample - in which the heater size was designed to be comparable to the water bubble characteristic length - had the largest critical heat flux (CHF) up to 300 Wcm -2 with a superheat ~ 13 degrees C. Additionally, CuIOs with a smaller heated area performed better in terms of reliability. This study offers preliminary insights into CuIOs degradation mechanisms, contributing to the development of more robust thermal management solutions. We expect that electroless plating of CuIOs with gold (Au), nickel (Ni), and atomic layer deposition (ALD) aluminum oxide (Al 2 O 3 ) in combination with appropriate application-specific coolants will further improve the reliability and lifetime of the CuIOs.
- Research Organization:
- National Renewable Energy Laboratory (NREL), Golden, CO (United States)
- Sponsoring Organization:
- USDOE Advanced Research Projects Agency - Energy (ARPA-E)
- DOE Contract Number:
- AC36-08GO28308
- OSTI ID:
- 2477750
- Report Number(s):
- NREL/CP-5400-92116; MainId:93894; UUID:c3fe311a-b58a-45a9-9fe7-99f831ca140b; MainAdminId:74280
- Country of Publication:
- United States
- Language:
- English
Similar Records
Mitigation of Boiling-Induced Thermal Degradation Using Microporous Nickel Inverse Opals Structures
Development of a Hybrid Single/Two-Phase Capillary-Based Micro-Cooler using Copper Inverse Opals Wick with Silicon 3D Manifold for High-Heat-Flux Cooling Application