Title: Ventilation or filtration? The use of gas-phase air filtration for compliance with ASRAE Standard 62

Conference ·
OSTI ID:227054

ASHRAE Standard 62, in its current form, employs two procedures to provide acceptable indoor air quality (IAQ) in buildings. These are the Ventilation Rate and Indoor Air Quality (IAQ) Procedures. This standard further endeavors to achieve the necessary balance between IAQ and energy consumption by specifying minimum ventilation rates and IAQ that will be acceptable to human occupants. The standard acknowledges that air cleaning, along with recirculation, is an effective means for controlling contaminants when using the IAQ Procedure. Employing this procedure allows the amount of outside ventilation air to be reduced below standard levels if it can be demonstrated that the resulting air quality meets the required criteria. More buildings are using, or will be using, gas-phase air filtration as part of their overall design for providing and maintaining acceptable IAQ. This trend is being seen in retrofit applications as well as new construction. Among the driving forces behind this are the increased awareness of people to their environment and how it may affect their well-being, legislative actions which are in effect or have been proposed, and, of course, that members of the legal community litigating complaints of sick building syndrome (SBS) and building-related illness (BRI). This paper will focus on the use of gas-phase air filtration for compliance with ASHRAE Standard 62 by using the IAQ Procedure. It will cover the requirements of using this procedure, the information required, and will describe several projects where this procedure was successfully used to realize both acceptable IAQ and energy savings.

OSTI ID:
227054
Report Number(s):
CONF-951173-; TRN: 96:000139-0018
Resource Relation:
Conference: 18. world energy engineering congress, Atlanta, GA (United States), 8-10 Nov 1995; Other Information: PBD: 1996; Related Information: Is Part Of Vision 2001: Energy & environmental engineering; PB: 638 p.
Country of Publication:
United States
Language:
English

Similar Records

Ventilation or filtration? The use of gas-phase air filtration for compliance with ASHRAE Standard 62
Journal Article · Mon Sep 01 00:00:00 EDT 1997 · Energy Engineering · OSTI ID:227054

Ventilation air flow measurement for ASHRAE standard 62-1989
Journal Article · Thu Oct 01 00:00:00 EDT 1992 · ASHRAE Journal (American Society of Heating, Refrigerating and Air-Conditioning Engineers); (United States) · OSTI ID:227054

ASHRAE and residential ventilation