Impact evaluation of a refrigeration control system installed at Columbia Colstor
This impact evaluation of a computer-based refrigeration control system (RCS) installed at Columbia Colstor in 1990 was conducted for the Bonneville Power Administration (Bonneville) by Pacific Northwest Laboratory (PNL). Concurrent with installing the RCS, the plant was expanded by adding 13,900 m{sup 2} (150,000 ft{sup 2} of storage space and five freeze tunnels. Because this project involved a significant plant expansion, it was ineligible for participation in Bonneville`s Energy $avings Plan Program (E$P). Therefore, a special contract was negotiated. This contract followed, to the extent possible, the E$P principles, adminstrative procedures, and acquisition payment. The primary objectives of this impact evaluation were to assess how much electrical energy is being saved at Columbia Colstor as a result of the Bonneville`s acquisition payment and to determine how much the savings cost Bonneville and the region. The impact of the project was evaluated with a combination of engineering analysis, billing analysis, financial analysis, interviews, and submittal reviews. Based on this impact evaluation, energy savings from this project are expected to be at least 4,130,700 kilowatt-hours/year (kWh/yr), or 0.47 average megawatts (aMW). Because the refrigeration system at Columbia Colstor provides cooling to both the storage rooms and the freeze tunnels, it i not possible to state savings on a per-ton basis. The project cost $287,528 to install, and Columbia Colstor received payment of $180,375 (1991 dollars) from Bonneville for the acquisition of energy savings. The real levelized cost of these energy savings to Bonneville is 4.5 mills/kWh (in 1993 dollars) over the project`s assumed 15-year life, and the real levelized cost to the region is 7.6 mills/kWh in 1993 dollars, not including transmission and distribution effects.
- Research Organization:
- Pacific Northwest Lab., Richland, WA (United States)
- Sponsoring Organization:
- USDOE, Washington, DC (United States)
- DOE Contract Number:
- AC06-76RL01830
- OSTI ID:
- 208394
- Report Number(s):
- PNL--9463; ON: DE96006838
- Country of Publication:
- United States
- Language:
- English
Similar Records
Impact evaluation of a refrigeration control system installed at Vitamilk Dairy, Incorporated under the Energy $avings Plan
Impact evaluation of a slush stock chest bypass installed at Scott Paper Company under the energy $avings plan
Impact evaluation of an induction furnace replacement under the Energy $avings Plan at Mackenzie Specialty Castings, Incorporated
Technical Report
·
Sat Dec 31 23:00:00 EST 1994
·
OSTI ID:50901
Impact evaluation of a slush stock chest bypass installed at Scott Paper Company under the energy $avings plan
Technical Report
·
Tue Jan 31 23:00:00 EST 1995
·
OSTI ID:79063
Impact evaluation of an induction furnace replacement under the Energy $avings Plan at Mackenzie Specialty Castings, Incorporated
Technical Report
·
Thu Mar 31 23:00:00 EST 1994
·
OSTI ID:10159861