Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Bi-Level Linear Programming Model for Automatic Load Shedding: A Distributed Wide-Area Measurement System-based Solution

Conference ·

Load shedding is currently implemented as a two-step based approach. In the first step, manual load shedding is taken place, were system operators, using estimates, inform distribution utilities of predicted stressful conditions. Information provided include the potential use of energy reserves, as well as load shedding amount. In a second step, automatic load shedding is done. The latter is realized using protection relays. While considering frequency variation, pre-defined values of load to be shed and correspondent number of stages for such to be realized are transformed into relay settings. Under-frequency protection relays use only local measurements towards decision making, thus operate in a decentralized architecture. Decision making is done in milliseconds plus breaker time. While this approach has provided much system reliability, considering the new smart grid paradigm, where system dynamics are much faster due to increasing renewable resources penetration, in some operating conditions it will generate sub-optimal solutions, such as islanding. Phasor measurement units provide a source of information which can be useful for this problem. Centralized architecture-based solutions for automatic load shedding, as present in the state-of-the-art, require though total processing times which are not acceptable for real-life implementation. In this work, considering the above, a bi-level linear programming model is presented. The model is implemented considering a distributed architecture while leveraging phasor measurement units data. The upper-level model estimates the current system state. Results of this model are embedded in a lower-level model, which decision variables are the location and load value to be shed. Easy-to-implement model, built-on the classic weighted least squares solution, highlight potential aspects towards real-life applications.

Research Organization:
Pacific Northwest National Laboratory (PNNL), Richland, WA (United States)
Sponsoring Organization:
USDOE
DOE Contract Number:
AC05-76RL01830
OSTI ID:
1963590
Report Number(s):
PNNL-SA-177286
Country of Publication:
United States
Language:
English

Similar Records

Proactive Frequency Stability Scheme via Bayesian Filters and Synchrophasors
Conference · Thu Aug 17 00:00:00 EDT 2023 · OSTI ID:1996331

Computer algorithm for selection of frequency relays for load shedding
Journal Article · Thu Dec 31 23:00:00 EST 1987 · IEEE Comput. Applicat. Power; (United States) · OSTI ID:6173546

Tri-Level Linear Programming Model for Automatic Load Shedding Using Spectral Clustering
Conference · Sun Mar 03 23:00:00 EST 2024 · OSTI ID:2319236