Title: Overall chilled water system energy consumption modeling and optimization

Journal Article · · Applied Energy
 [1];  [1];  [1]
  1. Indiana Univ.-Purdue Univ. Indianapolis (IUPUI), Indianapolis, IN (United States)

The emergence of increasingly affordable variable-speed drive technology has changed the approach used to control chilled water systems equipped with these drives. The purpose of this research was to develop an integrated chilled water modeling technique that can determine the optimal system setpoints and estimate the energy saving potential of chiller system. The chiller system equipped with Variable Frequency Drives (VFDs) on cooling tower fans and condenser water pumps. To accomplish the objective, physical component models of the centrifugal chiller, cooling tower and condenser water pump were established with the goal of incorporating the system’s condenser water flow rate and cooling tower fan speeds as optimization variables. Furthermore, a cooling load prediction algorithm was developed using a multiple non-linear regression model to approximate the building’s cooling load subject to a range of environmental conditions. The inputs and outputs of the individual component models were linked to estimate how adjusting the cooling tower fan and condenser water pump speed would influence the system’s comprehensive performance. Here, the overall system model was then optimized using a generalized reduced gradient optimization algorithm to determine the potential energy savings through speed control with VFDs and to ascertain a control logic strategy for the building automation system to operate the heating and cooling system. A case-study was performed on a single chiller system at a museum and the model was calibrated according to logged data collected over four months. Results showed that for the system analyzed, the energy saving of optimizing the cooling tower fan system was found to be 12–15%, while the energy saving potential of optimizing the condenser water pump with the cooling tower fan was negligible. Additionally, comparing different cooling tower fan control strategies showed that a wet-bulb approach-based cooling tower control strategy was shown to have the highest correlation to the optimized fan speed with an R2 of 0.924.

Research Organization:
Indiana Univ., Indianapolis, IN (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Advanced Manufacturing Office
Grant/Contract Number:
EE0007711
OSTI ID:
1866815
Journal Information:
Applied Energy, Vol. 299; ISSN 0306-2619
Publisher:
ElsevierCopyright Statement
Country of Publication:
United States
Language:
English

References (11)

A simplified methodology to optimize the cooling tower approach temperature control schedule in a cooling system journal November 2019
A study on an optimal approach temperature control strategy of condensing water temperature for energy saving journal May 2011
A simplified modeling of mechanical cooling tower for control and optimization of HVAC systems journal February 2007
HVAC system optimization––condenser water loop journal March 2004
Environmental performance and economic analysis of all-variable speed chiller systems with load-based speed control journal June 2009
Particle Swarm optimization for control operation of an all-variable speed water-cooled chiller plant journal February 2018
Real-time optimization of a chilled water plant with parallel chillers based on extremum seeking control journal December 2017
Cooling load prediction and optimal operation of HVAC systems using a multiple nonlinear regression model journal August 2019
Thermodynamic modeling of reciprocating chillers journal March 1994
How varying condenser coolant flow rate affects chiller performance: thermodynamic modeling and experimental confirmation journal September 2000
An algorithm for quadratic programming journal March 1956