Modeling the impact of GIC neutral blocking devices on distance protection relay operations for transmission lines
Journal Article
·
· Electric Power Systems Research
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
Geomagnetic Induced Current (GIC) blocking devices typically include a capacitor on the neutral grounding path of wye-configured transformers. This type of GIC blocking device was designed as an effective countermeasure to prevent possible damages caused on the power grid by geomagnetic storms, and by the slow-varying component of a high-altitude electromagnetic pulse (HEMP). The insertion of a capacitor in the transformer neutral impedes the establishment of GICs in lines terminated with wye-connected transformer windings. With the presence of a capacitively grounded neutral, however, it becomes important to evaluate that no adverse effects are introduced in the general grid operations. In this context, this study investigates the impact of GIC neutral blocking devices on the functionality of distance protection relays for different values of transformer neutral blocking capacitors, and at different transmission line voltages. This study was conducted with a real-time simulation platform, and the simulations were performed by introducing a phase-to-ground fault at different line locations, and by measuring the apparent impedance at the protection relay location. Finally, the results indicated that, for typical values of capacitance considered for GIC neutral blocking devices, the distance protection relay model operates properly, without requiring a modification of the relay settings.
- Research Organization:
- Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE
- Grant/Contract Number:
- AC05-00OR22725
- OSTI ID:
- 1607236
- Journal Information:
- Electric Power Systems Research, Journal Name: Electric Power Systems Research Journal Issue: C Vol. 180; ISSN 0378-7796
- Publisher:
- ElsevierCopyright Statement
- Country of Publication:
- United States
- Language:
- English
Similar Records
Impact assessment of geomagnetic induced current neutral blocking devices with power electronics sources on distance relay for 230 kV transmission lines
GIC mitigation; A neutral blocking/bypass device to prevent the flow of GIC in power systems
The effects of GIC on protective relaying
Journal Article
·
Thu Sep 25 00:00:00 EDT 2025
· Electric Power Systems Research
·
OSTI ID:3002581
GIC mitigation; A neutral blocking/bypass device to prevent the flow of GIC in power systems
Journal Article
·
Mon Jul 01 00:00:00 EDT 1991
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:5853441
The effects of GIC on protective relaying
Journal Article
·
Sun Mar 31 23:00:00 EST 1996
· IEEE Transactions on Power Delivery
·
OSTI ID:244806