Unintentional Islanding Detection Performance with Mixed DER Types

Technical Report ·
DOI:https://doi.org/10.2172/1463446· OSTI ID:1463446
 [1];  [1];  [1];  [1];  [2];  [2]
  1. Northern Plains Power Technologies, Brookings, SD (United States)
  2. Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)
Most inverters for use in distribution-connected distributed energy resource applications (distributed generation and energy storage) are tested and certified to detect and cease to energize unintentional islands on the electric grid. The requirements for the performance of islanding detection methods are specified in IEEE 1547-2018, and specified conditions for certification- type testing of islanding detection are defined in IEEE 1547.1. Such certification-type testing is designed to ensure a minimum level of confidence that these inverters will not island in field applications. However, individual inverter certification tests do not address interactions between dissimilar inverters or between inverter and synchronous machines that may occur in the field. This work investigates the performance of different inverter island detection methods for these two circumstances that are not addressed by the type testing: 1) combinations of different inverters using different types of islanding detection methods, and 2) combinations of inverters and synchronous generators. The analysis took into consideration voltage and frequency ride- through requirements as specified in IEEE 1547-2018, but did not consider grid support functionality such as voltage or frequency response. While the risk of islanding is low even in these cases, it is often difficult to deal with these scenarios in a simplified interconnection screening process. This type of analysis could provide a basis to establish a practical anti- islanding screening methodology for these complex scenarios, with the goal of reducing the number of required detailed studies. Eight generic Groups of islanding detection behavior are defined, and examples of each are used in the simulations. The results indicate that islanding detection methods lose effectiveness at significantly different rates as the composition of the distributed energy resources (DERs) varies, with some methods remaining highly effective over a wide range of conditions.
Research Organization:
Sandia National Laboratories (SNL-NM), Albuquerque, NM (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Renewable Power Office. Solar Energy Technologies Office; USDOE National Nuclear Security Administration (NNSA)
DOE Contract Number:
AC04-94AL85000; NA0003525
OSTI ID:
1463446
Report Number(s):
SAND--2018-8431; 666671
Country of Publication:
United States
Language:
English

Similar Records

Experimental Evaluation of PV Inverter Anti-Islanding with Grid Support Functions in Multi-Inverter Island Scenarios
Technical Report · Thu Jun 30 20:00:00 EDT 2016 · OSTI ID:1265055

Impacts of Inverter-Based Advanced Grid Support Functions on Islanding Detection
Conference · Sun Dec 11 23:00:00 EST 2016 · OSTI ID:1344442