Title: Evaluation of the Effective Moisture Penetration Depth Model for Estimating Moisture Buffering in Buildings

Technical Report ·
DOI:https://doi.org/10.2172/1219896· OSTI ID:1219896
 [1];  [1];  [1]
  1. National Renewable Energy Lab. (NREL), Golden, CO (United States)

This study examines the effective moisture penetration depth (EMPD) model, and its suitability for building simulations. The EMPD model is a compromise between the simple, inaccurate effective capacitance approach and the complex, yet accurate, finite-difference approach. Two formulations of the EMPD model were examined, including the model used in the EnergyPlus building simulation software. An error in the EMPD model we uncovered was fixed with the release of EnergyPlus version 7.2, and the EMPD model in earlier versions of EnergyPlus should not be used.