Design review report, 241-S-102 cover plate review
The design for the cover plate and lead plate for shielding on 241-S-102 was reviewed on 10/21/98. All Review Comment Record comments were resolved to the satisfaction of the reviewers. Additional comments were taken during the meeting and were also resolved. A design calculation for the Radiological Design Review Screening was presented as criteria for the use of 1 inch lead plate. The review concluded that the use of 2 inch steel plate and 1 inch lead plate provided the required safety function required by HNF-SD-WM-810-001, 5.3.2.20, Basis for Interim Operation. The design was approved with the incorporated comments as recorded on RCR's and meeting minutes.