Regulatory analysis for the resolution of Generic Issue 143: Availability of chilled water system and room cooling

Technical Report ·
DOI:https://doi.org/10.2172/10115062· OSTI ID:10115062
This report presents the regulatory analysis for Generic Issue (GI-143), {open_quotes}Availability of Chilled Water System and Room Cooling.{close_quotes} The heating, ventilating, and air conditioning (HVAC) systems and related auxiliaries are required to provide control of environmental conditions in areas in light water reactor (LWR) plants that contain safety-related equipment. In some plants, the HVAC and chilled water systems serve to maintain a suitable environment for both safety and non-safety-related areas. Although some plants have an independent chilled water system for the safety-related areas, the heat removal capability often depends on the operability of other supporting systems such as the service water system or the component cooling water system. The operability of safety-related components depends upon operation of the HVAC and chilled water systems to remove heat from areas containing the equipment. If cooling to dissipate the heat generated is unavailable, the ability of the safety-related equipment to operate as intended cannot be assured. Typical components or areas in the nuclear power plant that could be affected by the failure of cooling from HVAC or chilled water systems include the (1) emergency switchgear and battery rooms, (2) emergency diesel generator room, (3) pump rooms for residual heat removal, reactor core isolation cooling, high-pressure core spray, and low-pressure core spray, and (4) control room. The unavailability of such safety-related equipment or areas could cause the core damage frequency (CDF) to increase significantly.
Research Organization:
Nuclear Regulatory Commission, Washington, DC (United States). Div. of Safety Issue Resolution
Sponsoring Organization:
Nuclear Regulatory Commission, Washington, DC (United States)
OSTI ID:
10115062
Report Number(s):
NUREG--1427; ON: TI94005199
Country of Publication:
United States
Language:
English