Regulatory analysis for the resolution of Generic Issue 143: Availability of chilled water system and room cooling
This report presents the regulatory analysis for Generic Issue (GI-143), {open_quotes}Availability of Chilled Water System and Room Cooling.{close_quotes} The heating, ventilating, and air conditioning (HVAC) systems and related auxiliaries are required to provide control of environmental conditions in areas in light water reactor (LWR) plants that contain safety-related equipment. In some plants, the HVAC and chilled water systems serve to maintain a suitable environment for both safety and non-safety-related areas. Although some plants have an independent chilled water system for the safety-related areas, the heat removal capability often depends on the operability of other supporting systems such as the service water system or the component cooling water system. The operability of safety-related components depends upon operation of the HVAC and chilled water systems to remove heat from areas containing the equipment. If cooling to dissipate the heat generated is unavailable, the ability of the safety-related equipment to operate as intended cannot be assured. Typical components or areas in the nuclear power plant that could be affected by the failure of cooling from HVAC or chilled water systems include the (1) emergency switchgear and battery rooms, (2) emergency diesel generator room, (3) pump rooms for residual heat removal, reactor core isolation cooling, high-pressure core spray, and low-pressure core spray, and (4) control room. The unavailability of such safety-related equipment or areas could cause the core damage frequency (CDF) to increase significantly.
- Research Organization:
- Nuclear Regulatory Commission, Washington, DC (United States). Div. of Safety Issue Resolution
- Sponsoring Organization:
- Nuclear Regulatory Commission, Washington, DC (United States)
- OSTI ID:
- 10115062
- Report Number(s):
- NUREG--1427; ON: TI94005199
- Country of Publication:
- United States
- Language:
- English
Similar Records
Assessment of costs and benefits associated with resolution of Generic Safety Issue 143 -- Availability of heating, ventilation, and air conditioning and chilled water systems
Value impact analysis of Generic Issue 143, Availability of Heating, Ventilation, Air Conditioning (HVAC) and Chilled Water Systems
Value-impact assessment for resolution of generic safety issue 143 - availability of HVAC and chilled water systems
Journal Article
·
Tue Feb 28 23:00:00 EST 1995
· Nuclear Technology
·
OSTI ID:32002
Value impact analysis of Generic Issue 143, Availability of Heating, Ventilation, Air Conditioning (HVAC) and Chilled Water Systems
Technical Report
·
Sun Oct 31 23:00:00 EST 1993
·
OSTI ID:10106874
Value-impact assessment for resolution of generic safety issue 143 - availability of HVAC and chilled water systems
Conference
·
Tue Jan 31 23:00:00 EST 1995
·
OSTI ID:95667
Related Subjects
21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS
210200
22 GENERAL STUDIES OF NUCLEAR REACTORS
220900
HVAC SYSTEMS
NUCLEAR POWER PLANTS
POWER REACTORS
NONBREEDING
LIGHT-WATER MODERATED
NONBOILING WATER COOLED
REACTOR COOLING SYSTEMS
REACTOR SAFETY
RELIABILITY
SYSTEM FAILURE ANALYSIS
WATER COOLED REACTORS
210200
22 GENERAL STUDIES OF NUCLEAR REACTORS
220900
HVAC SYSTEMS
NUCLEAR POWER PLANTS
POWER REACTORS
NONBREEDING
LIGHT-WATER MODERATED
NONBOILING WATER COOLED
REACTOR COOLING SYSTEMS
REACTOR SAFETY
RELIABILITY
SYSTEM FAILURE ANALYSIS
WATER COOLED REACTORS