Value impact analysis of Generic Issue 143, Availability of Heating, Ventilation, Air Conditioning (HVAC) and Chilled Water Systems
- Pacific Northwest Lab., Richland, WA (United States)
This study evaluates the values (benefits) and impacts (costs) associated with potential resolutions to Generic Issue 143, ``Availability of HVAC and Chilled Water Systems.`` The study identifies vulnerabilities related to failures of HVAC, chilled water, and room cooling systems; develops estimates of room heatup rates and safety-related equipment vulnerabilities following losses of HVAC/room cooler systems; develops estimates of the core damage frequencies and public risks associated with failures of these systems; develops three proposed resolution strategies to this generic issue; and performs a value/impact analysis of the proposed resolutions. Existing probabilistic risk assessments for four representative plants, including one plant from each vendor, form the basis for the core damage frequency and public risk calculations. Both internal and external events were considered. It was concluded that all three proposed resolution strategies exceed the $1,000/person-rem cost-effectiveness ratio. Additional evaluations were performed to develop ``generic`` insights on potential design-related and configuration-related vulnerabilities and potential high-frequency ({approximately}1E-04/RY) accident sequences that involve failures of HVAC/room cooling functions. It was concluded that, although high-frequency accident sequences may exist at some plants, these high-frequency sequences are plant-specific in nature or have been resolved through hardware and/or operational changes. The plant-specific Individual Plant Examinations are an effective vehicle for identification and resolution of these plant-specific anomalies and hardware configurations.
- Research Organization:
- Nuclear Regulatory Commission, Washington, DC (United States). Div. of Safety Issue Resolution; Pacific Northwest Lab., Richland, WA (United States)
- Sponsoring Organization:
- Nuclear Regulatory Commission, Washington, DC (United States)
- DOE Contract Number:
- AC06-76RL01830
- OSTI ID:
- 10106874
- Report Number(s):
- NUREG/CR--6084; PNL--8750; ON: TI94003896
- Country of Publication:
- United States
- Language:
- English
Similar Records
Assessment of costs and benefits associated with resolution of Generic Safety Issue 143 -- Availability of heating, ventilation, and air conditioning and chilled water systems
Value-impact assessment for resolution of generic safety issue 143 - availability of HVAC and chilled water systems
Regulatory analysis for the resolution of Generic Issue 143: Availability of chilled water system and room cooling
Journal Article
·
Tue Feb 28 23:00:00 EST 1995
· Nuclear Technology
·
OSTI ID:32002
Value-impact assessment for resolution of generic safety issue 143 - availability of HVAC and chilled water systems
Conference
·
Tue Jan 31 23:00:00 EST 1995
·
OSTI ID:95667
Regulatory analysis for the resolution of Generic Issue 143: Availability of chilled water system and room cooling
Technical Report
·
Tue Nov 30 23:00:00 EST 1993
·
OSTI ID:10115062
Related Subjects
22 GENERAL STUDIES OF NUCLEAR REACTORS
220200
220900
AIR CONDITIONING
AUXILIARY WATER SYSTEMS
AVAILABILITY
COMPONENTS AND ACCESSORIES
COOLING SYSTEMS
COST BENEFIT ANALYSIS
DAMAGE
FAILURE MODE ANALYSIS
FAILURES
HEATING SYSTEMS
NUCLEAR POWER PLANTS
REACTOR CORES
REACTOR SAFETY
RISK ASSESSMENT
VENTILATION SYSTEMS
220200
220900
AIR CONDITIONING
AUXILIARY WATER SYSTEMS
AVAILABILITY
COMPONENTS AND ACCESSORIES
COOLING SYSTEMS
COST BENEFIT ANALYSIS
DAMAGE
FAILURE MODE ANALYSIS
FAILURES
HEATING SYSTEMS
NUCLEAR POWER PLANTS
REACTOR CORES
REACTOR SAFETY
RISK ASSESSMENT
VENTILATION SYSTEMS