Reactive capability limitation of synchronous machines
Journal Article
·
· IEEE Transactions on Power Systems (Institute of Electrical and Electronics Engineers); (United States)
- IRD Corp., Bethesda, MD (United States)
- Baltimore Gas and Electric Co., Baltimore, MD (United States)
Achievable generator reactive capability (GRC) is generally much less than indicated by manufacturers' reactive capability curves, due to constraints imposed by plant auxiliaries and the power system itself. The nature of these constraints is explained and a method for calculating them is provided and verified by field tests on a unit at high and low system voltage levels. Several recommendations are made to enhance the GRC of the tested unit.