skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Evaluation of the effect of pressurized bushings on seismic qualification of SF sub 6 circuit breakers

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
DOI:https://doi.org/10.1109/61.53107· OSTI ID:6731456
; ;  [1];  [2]
  1. Mitsubishi Electric Corp., Amagasaki, Hyogo (Japan)
  2. WM Power Products Inc., Pittsburgh, PA (US)

Stresses on the porcelain of high voltage switchgear under seismic vibration are statically biased by internal pressure. However, restrictions from the seismic test facility pose some difficulties in practical procedure of test with pressure. This paper discusses the effect of pressure on the strain and proposes an equivalent test method to simulate a pressurized condition without actually filling the SF{sub 6} gas to the operating pressure.

OSTI ID:
6731456
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA), Vol. 5:2; ISSN 0885-8977
Country of Publication:
United States
Language:
English