skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Composite rod insulators for ac power lines; Electrical performance of various designs at a coastal testing station

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
DOI:https://doi.org/10.1109/61.103691· OSTI ID:6343186
;  [1]
  1. Central Electricity Research Labs., Leatherhead (UK)

The electrical performance of thirty-six composite insulators - of four commercial types for each AC system level of 34.5 kV, 230 kV and 500 kV - has been determined at the CEGB insulator testing station, Brighton, England. The weathershed materials were epoxy-resin, ethylene propylene rubber and silicone rubber; half of the 230 kV insulators had no stress rings. Surface leakage current was recorded for surge levels of 25 mA, 150 mA and 500 mA; a special technique was developed to obtain the flashover statistics of the 500 kV insulators, thereby enabling performance of the composite insulator to be quantified relative to that of a string of cap and pin porcelain insulators of anti-fog design, the deterioration of the insulators was observed by making regular visual inspections. The practical consequences of the findings and the causes of the degradation are discussed.

OSTI ID:
6343186
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA), Vol. 5:4; ISSN 0885-8977
Country of Publication:
United States
Language:
English