Title: Reliability study: raw and make-up water system, Portsmouth Gaseous Diffusion Plant

Technical Report ·
OSTI ID:6089555

A reliability study for determining the ability of the raw and make-up water system to provide reliable and adequate service through the year 2000 has been completed. This study includes an evaluation of the well fields, X-608 Raw Water Pump House, X-605 Booster Station Complex, X-611 Water Treatment Complex, and the associated piping. The raw and make-up water system is in good overall condition, but to maintain this condition, the reliability study team made the following recommendations: (1) increase well field capacity; (2) replace certain speed reducers at X-611; (3) repair deteriorated poles, crossarms, and accessories on F-2 and W-1 feeders; (4) stabilize the landslide in vicinity of the 48 in. raw water main; and (5) initiate further investigation, testing, or engineering studies to correct deficiencies in the supervisory control system between well fields, pump house, and X-611, determine if the 2400 volt underground cables to X-608A wells should be replaced.

Research Organization:
Goodyear Atomic Corp., Piketon, OH (USA)
DOE Contract Number:
AC05-76OR00001
OSTI ID:
6089555
Report Number(s):
GAT-1034; ON: DE82000943; TRN: 82-000120
Country of Publication:
United States
Language:
English