Reliability study: raw and make-up water system, Portsmouth Gaseous Diffusion Plant
- comps.
A reliability study for determining the ability of the raw and make-up water system to provide reliable and adequate service through the year 2000 has been completed. This study includes an evaluation of the well fields, X-608 Raw Water Pump House, X-605 Booster Station Complex, X-611 Water Treatment Complex, and the associated piping. The raw and make-up water system is in good overall condition, but to maintain this condition, the reliability study team made the following recommendations: (1) increase well field capacity; (2) replace certain speed reducers at X-611; (3) repair deteriorated poles, crossarms, and accessories on F-2 and W-1 feeders; (4) stabilize the landslide in vicinity of the 48 in. raw water main; and (5) initiate further investigation, testing, or engineering studies to correct deficiencies in the supervisory control system between well fields, pump house, and X-611, determine if the 2400 volt underground cables to X-608A wells should be replaced.
- Research Organization:
- Goodyear Atomic Corp., Piketon, OH (USA)
- DOE Contract Number:
- AC05-76OR00001
- OSTI ID:
- 6089555
- Report Number(s):
- GAT-1034; ON: DE82000943; TRN: 82-000120
- Country of Publication:
- United States
- Language:
- English
Similar Records
Low-Risk and Cost-Effective Prior Savings Estimates for Large-Scale Energy Conservation Projects in Housing: Learning from the Fort Polk GHP Project
Reliability study: steam generation and distribution system, Portsmouth Gaseous Diffusion Plant
Related Subjects
42 ENGINEERING
PORTSMOUTH GASEOUS DIFFUSION PLANT
WATER SUPPLY
WATER TREATMENT PLANTS
RELIABILITY
OPERATION
PIPELINES
PUMPS
WELLS
GASEOUS DIFFUSION PLANTS
INDUSTRIAL PLANTS
ISOTOPE SEPARATION PLANTS
NATIONAL ORGANIZATIONS
NUCLEAR FACILITIES
US DOE
US ERDA
US ORGANIZATIONS
050501* - Nuclear Fuels- Uranium Enrichment- Gaseous Diffusion- (-1989)
420200 - Engineering- Facilities
Equipment