Title: Analysis of a harmonic overvoltage due to transformer saturation following load shedding on Hydro-Quebec - NYPA 765 kV interconnection

Journal Article · · IEEE (Institute of Electrical and Electronics Engineers) Transactions on Power Delivery; (USA)
DOI:https://doi.org/10.1109/61.107304· OSTI ID:5128924

This paper presents an analysis of the harmonic overvoltage recorded on the interconnection between Hydro-Quebec and the New York Power Authority (NYPA) in the Chateauguay area. The overvoltage was caused by transformer saturation, following tripping of the 765-kV transmission line linking both systems. The EMTP simulation yielded good agreement with field measurements and was valuable in re-evaluating operating practices at the Chateauguay station.

OSTI ID:
5128924
Journal Information:
IEEE (Institute of Electrical and Electronics Engineers) Transactions on Power Delivery; (USA), Vol. 5:1; ISSN 0885-8977
Country of Publication:
United States
Language:
English

Similar Records

Hydro-Quebec's high-voltage interconnections
Journal Article · Mon Jun 01 00:00:00 EDT 1992 · IEEE Power Engineering Review (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:5128924

Statistical switching overvoltage analysis of the first B. C. Hydro phase shifting transformer using the electromagnetic transients program
Journal Article · Thu Nov 01 00:00:00 EST 1990 · IEEE Transactions on Power Systems (Institute of Electrical and Electronics Engineers); (USA) · OSTI ID:5128924

A 735 kV shunt reactors automatic switching system for Hydro-Quebec network
Journal Article · Fri Nov 01 00:00:00 EST 1996 · IEEE Transactions on Power Systems · OSTI ID:5128924