Title: Detection of smoldering combustion of coal with an odor meter

Conference ·
OSTI ID:41723
 [1]
  1. Pittsburgh Research Center, PA (United States)

A commercially available odor meter was evaluated as a detector of smoldering coal combustion, and compared with incipient carbon monoxide (CO) and hydrogen sulfide (H{sub 2}S) detection and a commercially available ionization-type smoke detector. Ten smoldering coal combustion experiments were conducted. For eight of the experiments, Pittsburgh seam coal with an average particle diameter of approximately 5 cm was heated by embedded electrical strip heaters. For two of the experiments mine size Pittsburgh seam coal was heated. Heating rates of 0.5, 0.8, and 1.1. kw were selected to provide experimental conditions characteristic of very slow and moderately fast heating for coal sample mass between 3 and 10 kg. It was found that the odor meter and smoke detector alarm had a good correlation, with the odor meter alarm occurring prior to the smoke alarm in four of the ten experiments. The odor meter gave an increase in its output signal above ambient equivalent to detecting 1 ppm of H{sub 2}S (ten times the odor threshold of H{sub 2}S) as an alarm value. This observed odor meter response occurred prior to the electrochemical detection of H{sub 2}S for five of the six experiments for which it was evaluated. In all six experiments for which the smoke optical density was evaluated, it was less than 0.023 m{sup -1} prior to the odor meter reaching alarm. In each of the eight experiments with 5 cm diameter coal particles the CO exceeded 5 ppm at odor meter alarm, while for the two experiments with mine size coal the CO was less than 3 ppm at odor meter alarm. The odor meter, as tested, is not a significant improvement over smoke and CO detectors. Because the odor meter responds to a variety of chemical compounds, with suitable modification and increased sensitivity it may be useful for detection of mine fires and thereby enhance mine safety.

OSTI ID:
41723
Report Number(s):
CONF-9407171-; TRN: 95:003332-0018
Resource Relation:
Conference: 12. West Virginia University (WVU) international mining electrotechnology conference, Morgantown, WV (United States), 27-29 Jul 1994; Other Information: PBD: 1995; Related Information: Is Part Of The 12th West Virginia University international mining electrotechnology conference; PB: 168 p.
Country of Publication:
United States
Language:
English

Similar Records

Diesel-discriminating detector response to smoldering fires
Journal Article · Fri Jan 01 00:00:00 EST 1993 · Information Circular - United States, Bureau of Mines; (United States) · OSTI ID:41723

Mine fire detection in the presence of diesel emissions
Conference · Thu Jul 01 00:00:00 EDT 1999 · OSTI ID:41723

Diesel-discriminating detector response to smoldering fires. Information circular/1993
Technical Report · Mon Dec 07 00:00:00 EST 1992 · OSTI ID:41723