Title: Analysis the configuration of earthing system based on high-low and low-high soil structure

Journal Article · · AIP Conference Proceedings
DOI:https://doi.org/10.1063/1.4915857· OSTI ID:22391686
; ; ; ;  [1]
  1. Faculty of Electrical Engineering, Universiti Teknikal Malaysia Melaka (UTeM), Hang Tuah Jaya, 76100 Durian Tunggal, Melaka (Malaysia)

Each TNB transmission tower requires a tower footing resistance (TFR) with a lower grounding resistance value that depends on the transmission line voltage. For 132kV and 275kV tower, the TFR must less than 10Ω and 500kV tower must less than 5Ω. The TFR is changeable with variable factors such as soil resistivity. Low TFR provides essential protection to the fault such as lightning strike that may occur at any time. The fault current flow to the lowest resistance path and easily disperses to earth. Back flashover voltage across the insulator of transmission lines may occur when the TFR is high. The TFR is influenced by soil resistivity. There are three parameters affecting the soil resistivity; moisture content, salt content and temperature of the soil. High moisture content in soil will reduce the soil resistivity and resultant low TFR. Small scale moisture control by using Micro Reservoir (MR) irrigation with semi-permeable membranes have the power to offer the stable moisture in soil. By using osmosis concept, it is the process of net movement of water molecules from high potential water to lower potential water though a semi permeable membrane. The MR can withstand for 3 to 5 days without continuous water supply. The MR installed in the centre of the tower that contains a multiple parallel of electrode rods. The concentrated of electrode rods grounding configuration with a combination of MR will improve the TFR even at multilayer soil. As a result, MR gives a little improvement to TFR. The MR in area of concentrated electrode rod configuration to ensure the soil always wet and moist at all times. The changes in soil affect the tower-footing-resistance. The tower-footing-resistance measurement at afternoon is higher than at evening because of the temperature and moisture content in soil is change due to sun radiation.

OSTI ID:
22391686
Journal Information:
AIP Conference Proceedings, Vol. 1660, Issue 1; Conference: ICoMEIA 2014: International Conference on Mathematics, Engineering and Industrial Applications 2014, Penang (Malaysia), 28-30 May 2014; Other Information: (c) 2015 AIP Publishing LLC; Country of input: International Atomic Energy Agency (IAEA); ISSN 0094-243X
Country of Publication:
United States
Language:
English

Similar Records

Development of a lightning current waveform measuring system for 500kV overhead transmission lines
Journal Article · Sat Jul 01 00:00:00 EDT 1989 · IEEE Trans. Power Del.; (United States) · OSTI ID:22391686

Development of a system for measuring lightning voltage waveforms on insulator strings for 500KV overhead transmission lines
Journal Article · Mon Oct 01 00:00:00 EDT 1990 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) · OSTI ID:22391686

Environmental factors affecting corrosion of munitions
Conference · Sun Dec 31 00:00:00 EST 1995 · OSTI ID:22391686