skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Submerged Medium Voltage Cable Systems at Nuclear Power Plants: A Review of Research Efforts Relevant to Aging Mechanisms and Condition Monitoring

Technical Report ·
DOI:https://doi.org/10.2172/1177756· OSTI ID:1177756

In a submerged environment, power cables may experience accelerated insulation degradation due to water-related aging mechanisms. Direct contact with water or moisture intrusion in the cable insulation system has been identified in the literature as a significant aging stressor that can affect performance and lifetime of electric cables. Progressive reduction of the dielectric strength is commonly a result of water treeing which involves the development of permanent hydrophilic structures in the insulation coinciding with the absorption of water into the cable. Water treeing is a phenomenon in which dendritic microvoids are formed in electric cable insulation due to electrochemical reactions, electromechanical forces, and diffusion of contaminants over time. These reactions are caused by the combined effects of water presence and high electrical stresses in the material. Water tree growth follows a tree-like branching pattern, increasing in volume and length over time. Although these cables can be “dried out,” water tree degradation, specifically the growth of hydrophilic regions, is believed to be permanent and typically worsens over time. Based on established research, water treeing or water induced damage can occur in a variety of electric cables including XLPE, TR-XLPE and other insulating materials, such as EPR and butyl rubber. Once water trees or water induced damage form, the dielectric strength of an insulation material will decrease gradually with time as the water trees grow in length, which could eventually result in failure of the insulating material. Under wet conditions or in submerged environments, several environmental and operational parameters can influence water tree initiation and affect water tree growth. These parameters include voltage cycling, field frequency, temperature, ion concentration and chemistry, type of insulation material, and the characteristics of its defects. In this effort, a review of academic and industrial literature was performed to identify: 1) findings regarding the degradation mechanisms of submerged cabling and 2) condition monitoring methods that may prove useful in predicting the remaining lifetime of submerged medium voltage power cables. The research was conducted by a multi-disciplinary team, and sources included official NRC reports, national laboratory reports, IEEE standards, conference and journal proceedings, magazine articles, PhD dissertations, and discussions with experts. The purpose of this work was to establish the current state-of-the-art in material degradation modeling and cable condition monitoring techniques and to identify research gaps. Subsequently, future areas of focus are recommended to address these research gaps and thus strengthen the efficacy of the NRC’s developing cable condition monitoring program. Results of this literature review and details of the testing recommendations are presented in this report.

Research Organization:
Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)
Sponsoring Organization:
Nuclear Regulatory Commission (NRC), Rockville, MD (United States)
DOE Contract Number:
AC04-94AL85000
OSTI ID:
1177756
Report Number(s):
SAND-2015-1794; 579628
Country of Publication:
United States
Language:
English