Exergy Analysis of a Two-Stage Ground Source Heat Pump with a Vertical Bore for Residential Space Conditioning under Simulated Occupancy
Abstract
This twelve-month field study analyzes the performance of a 7.56W (2.16- ton) water-to-air-ground source heat pump (WA-GSHP) to satisfy domestic space conditioning loads in a 253 m2 house in a mixed-humid climate in the United States. The practical feasibility of using the ground as a source of renewable energy is clearly demonstrated. Better than 75% of the energy needed for space heating was extracted from the ground. The average monthly electricity consumption for space conditioning was only 40 kWh at summer and winter thermostat set points of 24.4°C and 21.7°C, respectively. The WA-GSHP shared the same 94.5 m vertical bore ground loop with a separate water-to-water ground-source heat pump (WW-GSHP) for meeting domestic hot water needs in the same house. Sources of systemic irreversibility, the main cause of lost work are identified using Exergy and energy analysis. Quantifying the sources of Exergy and energy losses is essential for further systemic improvements. The research findings suggest that the WA-GSHPs are a practical and viable technology to reduce primary energy consumption and greenhouse gas emissions under the IECC 2012 Standard, as well as the European Union (EU) 2020 targets of using renewable energy resources.
- Authors:
-
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
- Publication Date:
- Research Org.:
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States). Building Technologies Research and Integration Center (BTRIC)
- Sponsoring Org.:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
- OSTI Identifier:
- 1190749
- Alternate Identifier(s):
- OSTI ID: 1247579
- Grant/Contract Number:
- AC05-00OR22725
- Resource Type:
- Accepted Manuscript
- Journal Name:
- Applied Energy
- Additional Journal Information:
- Journal Volume: 155; Journal ID: ISSN 0306-2619
- Publisher:
- Elsevier
- Country of Publication:
- United States
- Language:
- English
- Subject:
- 15 GEOTHERMAL ENERGY; Renewable Energy; Second Law; Thermodynamics; Availability; Geothermal; Ground-source
Citation Formats
Ally, Moonis Raza, Munk, Jeffrey D., Baxter, Van D., and Gehl, Anthony C. Exergy Analysis of a Two-Stage Ground Source Heat Pump with a Vertical Bore for Residential Space Conditioning under Simulated Occupancy. United States: N. p., 2015.
Web. doi:10.1016/j.apenergy.2015.06.004.
Ally, Moonis Raza, Munk, Jeffrey D., Baxter, Van D., & Gehl, Anthony C. Exergy Analysis of a Two-Stage Ground Source Heat Pump with a Vertical Bore for Residential Space Conditioning under Simulated Occupancy. United States. https://doi.org/10.1016/j.apenergy.2015.06.004
Ally, Moonis Raza, Munk, Jeffrey D., Baxter, Van D., and Gehl, Anthony C. Fri .
"Exergy Analysis of a Two-Stage Ground Source Heat Pump with a Vertical Bore for Residential Space Conditioning under Simulated Occupancy". United States. https://doi.org/10.1016/j.apenergy.2015.06.004. https://www.osti.gov/servlets/purl/1190749.
@article{osti_1190749,
title = {Exergy Analysis of a Two-Stage Ground Source Heat Pump with a Vertical Bore for Residential Space Conditioning under Simulated Occupancy},
author = {Ally, Moonis Raza and Munk, Jeffrey D. and Baxter, Van D. and Gehl, Anthony C.},
abstractNote = {This twelve-month field study analyzes the performance of a 7.56W (2.16- ton) water-to-air-ground source heat pump (WA-GSHP) to satisfy domestic space conditioning loads in a 253 m2 house in a mixed-humid climate in the United States. The practical feasibility of using the ground as a source of renewable energy is clearly demonstrated. Better than 75% of the energy needed for space heating was extracted from the ground. The average monthly electricity consumption for space conditioning was only 40 kWh at summer and winter thermostat set points of 24.4°C and 21.7°C, respectively. The WA-GSHP shared the same 94.5 m vertical bore ground loop with a separate water-to-water ground-source heat pump (WW-GSHP) for meeting domestic hot water needs in the same house. Sources of systemic irreversibility, the main cause of lost work are identified using Exergy and energy analysis. Quantifying the sources of Exergy and energy losses is essential for further systemic improvements. The research findings suggest that the WA-GSHPs are a practical and viable technology to reduce primary energy consumption and greenhouse gas emissions under the IECC 2012 Standard, as well as the European Union (EU) 2020 targets of using renewable energy resources.},
doi = {10.1016/j.apenergy.2015.06.004},
journal = {Applied Energy},
number = ,
volume = 155,
place = {United States},
year = {Fri Jun 26 00:00:00 EDT 2015},
month = {Fri Jun 26 00:00:00 EDT 2015}
}
Web of Science
Works referenced in this record:
Exergy analysis and operational efficiency of a horizontal ground-source heat pump system operated in a low-energy test house under simulated occupancy conditions
journal, June 2012
- Ally, Moonis R.; Munk, Jeffrey D.; Baxter, Van D.
- International Journal of Refrigeration, Vol. 35, Issue 4
Exergy and energy analysis of a ground-source heat pump for domestic water heating under simulated occupancy conditions
journal, August 2013
- Ally, Moonis R.; Munk, Jeffrey D.; Baxter, Van D.
- International Journal of Refrigeration, Vol. 36, Issue 5
Study on hybrid ground-coupled heat pump system for air-conditioning in hot-weather areas like Hong Kong
journal, September 2010
- Man, Yi; Yang, Hongxing; Wang, Jinggang
- Applied Energy, Vol. 87, Issue 9
Geothermal heat pump systems: Status review and comparison with other heating options
journal, January 2013
- Self, Stuart J.; Reddy, Bale V.; Rosen, Marc A.
- Applied Energy, Vol. 101
Underground water-source loop heat-pump air-conditioning system applied in a residential building in Beijing
journal, December 2005
- Chen, Chao; Sun, Feng-ling; Feng, Lei
- Applied Energy, Vol. 82, Issue 4
A study on energy and CO2 saving potential of ground source heat pump system in India
journal, April 2014
- Sivasakthivel, T.; Murugesan, K.; Sahoo, P. K.
- Renewable and Sustainable Energy Reviews, Vol. 32
Comprehensive exergy analysis of a ground-source heat pump system for both building heating and cooling modes
journal, December 2009
- Bi, Yuehong; Wang, Xinhong; Liu, Yun
- Applied Energy, Vol. 86, Issue 12
Experimental study of vertical ground-source heat pump performance evaluation for cold climate in Turkey
journal, April 2011
- Ozyurt, Omer; Ekinci, Dundar Arif
- Applied Energy, Vol. 88, Issue 4
Experimental study of a closed loop vertical ground source heat pump system
journal, March 2003
- Hepbasli, Arif; Akdemir, Ozay; Hancioglu, Ebru
- Energy Conversion and Management, Vol. 44, Issue 4
Experimental performance evaluation of a closed-loop vertical ground source heat pump in the heating mode using energy analysis method
journal, December 2007
- Kara, Yusuf Ali
- International Journal of Energy Research, Vol. 31, Issue 15
Vertical-borehole ground-coupled heat pumps: A review of models and systems
journal, January 2010
- Yang, H.; Cui, P.; Fang, Z.
- Applied Energy, Vol. 87, Issue 1
Performance and economic feasibility of ground source heat pumps in cold climate
journal, August 1997
- Healy, P. F.; Ugursal, V. I.
- International Journal of Energy Research, Vol. 21, Issue 10
Works referencing / citing this record:
Comparative Analysis of Different Methodologies Used to Estimate the Ground Thermal Conductivity in Low Enthalpy Geothermal Systems
journal, May 2019
- Sáez Blázquez, Cristina; Martín Nieto, Ignacio; Farfán Martín, Arturo
- Energies, Vol. 12, Issue 9