Achieving Energy Savings with Highly-Controlled Lighting in an Open-Plan Office

Technical Report ·
DOI:https://doi.org/10.2172/986324· OSTI ID:986324

An installation in a Federal building tested the effectiveness of a highly-controlled, workstation-specific lighting retrofit. The study took place in an open-office area with 86 cubicles and low levels of daylight. Each cubicle was illuminated by a direct/indirectpendant luminaire with three 32 watt lamps, two dimmable DALI ballasts, and an occupancy sensor. A centralized control system programmed all three lamps to turn on and off according to occupancy on a workstation-by-workstation basis. Field measurements taken over the course of several monthsdemonstrated 40% lighting energy savings compared to a baseline without advanced controls that conforms to GSA's current retrofit standard. A photometric analysis found that the installation provided higher desktop light levels than the baseline, while an occupant survey found that occupants in general preferred the lighting system to thebaseline.Simple payback is fairly high; projects that can achieve lower installation costs and/or higher energy savings and those in which greenhouse gas reduction and occupant satisfaction are significant priorities provide the ideal setting for workstation-specific lighting retrofits.

Research Organization:
Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US)
Sponsoring Organization:
Environmental Energy Technologies Division
DOE Contract Number:
AC02-05CH11231
OSTI ID:
986324
Report Number(s):
LBNL-3831E
Country of Publication:
United States
Language:
English

Similar Records

The Advantage of Highly Controlled Lighting for Offices and Commercial Buildings
Conference · Sun Aug 17 00:00:00 EDT 2008 · OSTI ID:973099

Adapting Wireless Technology to Lighting Control and Environmental Sensing
Technical Report · Sat Oct 01 00:00:00 EDT 2005 · OSTI ID:860860

Adapting Wireless Technology to Lighting Control and Environmental Sensing
Technical Report · Sun Apr 30 00:00:00 EDT 2006 · OSTI ID:920583