Electrical Energy and Demand Savings from a Geothermal Heat Pump ESPC at Fort Polk, LA

Journal Article · · Transactions / American Society of Heating, Refrigerating and Air-Conditioning Engineers
OSTI ID:978709

At Fort Polk, Louisiana, the space-conditioning systems of an entire city (4,003 military family housing units) have been converted to geothermal heat pumps (GHPs) under an energy savings performance contract. At the same time, other efficiency measures, such as compact fluorescent lights, low-flow hot water outlets, and attic insulation, were installed. Pre- and post-retrofit data were taken at 15-minute intervals on energy flows through the electrical distribution feeders that serve the family housing areas of the post. Fifteen-minute interval data were also taken on energy use from a sample of the residences. The analysis presented in this paper shows that for a typical meteorological year, the retrofits result in an electrical energy savings of approximately 25.6 million kWh, or 32.4% of the pre-retrofit electrical use in family housing. Peak electrical demand has also been reduced by about 6.8 MW, which is 40% of pre-retrofit peak demand. In addition, the retrofits save about 260,000 therms per year of natural gas. It should be noted that the energy savings presented in this document are the 'apparent' energy savings observed in the monitored data and are not to be mistaken for the 'contracted' energy savings used as the basis for payments. To determine the 'contracted' energy savings, the 'apparent' energy savings may require adjustments for such things as changes in indoor temperature performance criteri, addition of ceiling fans, and other factors.

Research Organization:
Oak Ridge National Laboratory (ORNL)
DOE Contract Number:
AC05-00OR22725
OSTI ID:
978709
Journal Information:
Transactions / American Society of Heating, Refrigerating and Air-Conditioning Engineers, Journal Name: Transactions / American Society of Heating, Refrigerating and Air-Conditioning Engineers Vol. 103
Country of Publication:
United States
Language:
English

Similar Records

Electrical energy and demand savings from a geothermal heat pump energy savings performance contract at Ft. Polk, LA
Technical Report · Sun Jun 01 00:00:00 EDT 1997 · OSTI ID:658213

Geothermal Heat Pump Energy Savings Performance Contract at Fort Polk, LA: Lessons Learned
Journal Article · Sun Jun 01 00:00:00 EDT 1997 · Transactions / American Society of Heating, Refrigerating and Air-Conditioning Engineers · OSTI ID:978710

Geothermal heat pump energy savings performance contract at Fort Polk, LA: Lessons learned
Conference · Fri Aug 01 00:00:00 EDT 1997 · OSTI ID:510348