Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Pacific Northwest GridWise™ Testbed Demonstration Projects; Part II. Grid Friendly™ Appliance Project

Technical Report ·
DOI:https://doi.org/10.2172/926122· OSTI ID:926122
Fifty residential electric water heaters and 150 new residential clothes dryers were modified to respond to signals received from underfrequency, load-shedding appliance controllers. Each controller monitored the power-grid voltage signal and requested that electrical load be shed by its appliance whenever electric power-grid frequency fell below 59.95 Hz. The controllers and their appliances were installed and monitored for more than a year at residential sites at three locations in Washington and Oregon. The controllers and their appliances responded reliably to each shallow underfrequency event—an average of one event per day—and shed their loads for the durations of these events. Appliance owners reported that the appliance responses were unnoticed and caused little or no inconvenience for the homes’ occupants.
Research Organization:
Pacific Northwest National Laboratory (PNNL), Richland, WA (US)
Sponsoring Organization:
USDOE
DOE Contract Number:
AC05-76RL01830
OSTI ID:
926122
Report Number(s):
PNNL-17079; TD5007130
Country of Publication:
United States
Language:
English

Similar Records

Results of the Grid Friendly Appliance Project
Conference · Wed Apr 14 00:00:00 EDT 2010 · OSTI ID:977318

Pacific Northwest GridWise™ Testbed Demonstration Projects; Part I. Olympic Peninsula Project
Technical Report · Tue Jan 08 23:00:00 EST 2008 · OSTI ID:926113

Grid Friendly Appliances – Load-side Solution for Congestion Management
Conference · Sun May 21 00:00:00 EDT 2006 · OSTI ID:900208