Title: DoD Climate Change Fuel Cell Program

Abstract

A grant was awarded to PPL EnergyPlus, LLC for two (2) 250kW Molten Carbonate Fuel Cells at Pepperidge Farm, Inc. on 9/30/03. Pepperidge Farm subsequently signed a contract for one 250kW fuel cell. A request was made and granted to apply the award for the second fuel cell to the Sheraton New York Hotel & Towers (see attached email). This report discusses the first year of operation of a fuel cell power plant located at Pepperidge Farm, Inc., Bloomfield, Connecticut and a fuel cell power plant located at Sheraton New York Hotel & Towers, New York, New York. PPL EnergyPlus, LLC installed the plants under a contract with Pepperidge Farm and Starwood Hotels & Resorts Worldwide, Inc. Two DFC 300 fuel cells, manufactured by FuelCell Energy, Inc. of Danbury, CT were selected for the project. The fuel cell located at Pepperidge Farm successfully operated from January 16, 2006 to January 15, 2007. The fuel cell located at Sheraton New York Hotel & Tower successfully operated from May 19, 2005 to May 18, 2006.This report discusses the performance of these plants during these periods.

Authors:
Publication Date:
Research Org.:
Ppl Energyplus, Llc
Sponsoring Org.:
USDOE
OSTI Identifier:
920083
DOE Contract Number:
FG26-03NT42022
Resource Type:
Technical Report
Country of Publication:
United States
Language:
English
Subject:
30 DIRECT ENERGY CONVERSION; AWARDS; CLIMATES; CONNECTICUT; FARMS; FUEL CELL POWER PLANTS; FUEL CELLS; HOTELS; MOLTEN CARBONATE FUEL CELLS; NEW YORK; PERFORMANCE

Citation Formats

Steven A. Gabrielle. DoD Climate Change Fuel Cell Program. United States: N. p., 2007. Web. doi:10.2172/920083.
Steven A. Gabrielle. DoD Climate Change Fuel Cell Program. United States. doi:10.2172/920083.
Steven A. Gabrielle. Mon . "DoD Climate Change Fuel Cell Program". United States. doi:10.2172/920083. https://www.osti.gov/servlets/purl/920083.
@article{osti_920083,
title = {DoD Climate Change Fuel Cell Program},
author = {Steven A. Gabrielle},
abstractNote = {A grant was awarded to PPL EnergyPlus, LLC for two (2) 250kW Molten Carbonate Fuel Cells at Pepperidge Farm, Inc. on 9/30/03. Pepperidge Farm subsequently signed a contract for one 250kW fuel cell. A request was made and granted to apply the award for the second fuel cell to the Sheraton New York Hotel & Towers (see attached email). This report discusses the first year of operation of a fuel cell power plant located at Pepperidge Farm, Inc., Bloomfield, Connecticut and a fuel cell power plant located at Sheraton New York Hotel & Towers, New York, New York. PPL EnergyPlus, LLC installed the plants under a contract with Pepperidge Farm and Starwood Hotels & Resorts Worldwide, Inc. Two DFC 300 fuel cells, manufactured by FuelCell Energy, Inc. of Danbury, CT were selected for the project. The fuel cell located at Pepperidge Farm successfully operated from January 16, 2006 to January 15, 2007. The fuel cell located at Sheraton New York Hotel & Tower successfully operated from May 19, 2005 to May 18, 2006.This report discusses the performance of these plants during these periods.},
doi = {10.2172/920083},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Mon Apr 30 00:00:00 EDT 2007},
month = {Mon Apr 30 00:00:00 EDT 2007}
}

Technical Report:

Save / Share:
  • This report discusses the first year of operation of a fuel cell power plant located at the Ocean County College, Toms River, New Jersey. PPL EnergyPlus, LLC installed the plant under a contract with Ocean County College. A DFC{reg_sign}300 fuel cell, manufactured by Fuel Cell Energy, Inc. of Danbury, CT was selected for the project. The fuel cell successfully operated from January 1, 2004 to December 31, 2004. This report discusses the performance of the plant during this period. Ocean County College's decision to contract for use of a fuel cell at the college reflects the institution's commitment to managingmore » energy costs, exercising environmental leadership, and leveraging innovative technologies to accomplish its energy and environmental goals. Ocean County College's director of facilities was interested in finding new energy cost reduction opportunities that could build on the institution's growing reputation for commitment to energy efficiency and environmental quality while exploring new technologies. This combination of goals positioned Ocean County College to value the prospect of installing a fuel cell as a demonstration project that could deliver on its commitment. PPL EnergyPlus, LLC developed the project and Millennium Builders, a PPL company, was chosen as the general contractor for the project. PPL and Ocean County College worked very closely with Jersey Central Power and Light (JCP&L) and New Jersey Natural Gas (NJNG) Company to assure integration of the fuel cell with the local utilities. The 250 kW molten carbonate fuel cell (MCFC) and its balance of plant is contained in an all-weather container located just outside the college's Instructional Building on a cement pad in a fenced-in 30 x 50 foot area in close proximity to the college's boiler and electrical rooms. Cables and piping bring power and hot water from the fuel cell into these interior control areas. The unit's electrical output is fed onto the college's main circuit while the hot water flows from the fuel cell to the college through a closed loop equipped with internal heat exchangers mounted on a custom skid in the boiler room. Fresh make-up water for the fuel cell's reverse osmosis equipment is piped separately from the boiler room out to the fuel cell. The fuel cell operates in parallel with the local electric utility's distribution system that serves the general area. The interconnection design relies on the grid protection components that come as standard equipment in the FCE unit design. Ultimately, the only substantive approval for the installation was for the parallel interconnection with the grid, provided by Jersey Central Power & Light. The utility had a well-defined set of interconnection requirements and procedures for units under 5 MW, and the approval process went smoothly and caused little delays. The primary liaison with PPL and the college was the utility's account representative. PPL and the college report that JCP&L was quite supportive of the project. The 60 percent reimbursement of installed costs was made through the New Jersey Clean Energy Fund, which is in turn funded through utility contributions. The Department of Energy provided an additional $250,000 grant under the Department of Defense fuel cell buy down program. PPL started testing the fuel cell on October 31, 2003. Final acceptance of the fuel cell was completed on December 21, 2003. Following several months of start-up activities, a high availability factor and few operating difficulties have marked operations during the first year.« less
  • Since the beginning of the Year 2001, the Saint-Agnes-Hospital in Bocholt, Germany, operates a phosphoric acid fuel cell (PAFC) to provide the base load of electrical power as well as heat in Winter and air conditioning in Summer. The project was made possible by federal funding from the U.S. Department of Energy as well as by a strategic alliance with the local utility company, the Bocholter Energie- und Wasserversorgung GmbH (BEW), and with the gas supplier of BEW, the Thyssengas GmbH. The fuel cell power plant is combined with an absorption chiller. It is highly efficient and has an excellentmore » power to heat ratio. The operation during the first Year went smoothly and nearly free of trouble.« less
  • Congress agreed to provide funding to DOD for a competitive, cost- shared, near-term, Climate Change Fuel Cell program. Objectives are to reduce greenhouse gas emissions through the efficient use of fossil fuels, accelerate fuel cell commercialization for US manufacturers, and satisfy DOD goals for the environment, readiness, and economy, through activities which would stimulate end-user applications. Fuel cell power plants with combined capacity between 100 and 3,000 kW are covered.
  • ChevronTexaco has successfully operated a 200 kW PC25C phosphoric acid fuel cell power plant at the corporate data center in San Ramon, California for the past two years and seven months following installation in December 2001. This site was chosen based on the ability to utilize the combined heat (hot water) and power generation capability of this modular fuel cell power plant in an office park setting . In addition, this project also represents one of the first commercial applications of a stationary fuel cell for a mission critical data center to assess power reliability benefits. This fuel cell powermore » plant system has demonstrated outstanding reliability and performance relative to other comparably sized cogeneration systems.« less
  • This report covers the first year of operation of a fuel cell power plant, installed by PPL Spectrum, Inc. (PPL) under contract with the United States Coast Guard (USCG), Research and Development Center (RDC). The fuel cell was installed at Air Station Cape Cod in Bourne, MA. The project had the support of the Massachusetts Technology Collaborative (MTC), the Department of Energy (DOE), and Keyspan Energy. PPL selected FuelCell Energy, Inc. (FCE) and its fuel cell model DFC{reg_sign}300 for the contract. Grant contributions were finalized and a contract between PPL and the USCG for the manufacture, installation, and first year'smore » maintenance of the fuel cell was executed on September 24, 2001. As the prime contractor, PPL was responsible for all facets of the project. All the work was completed by PPL through various subcontracts, including the primary subcontract with FCE for the manufacture, delivery, and installation of the fuel cell. The manufacturing and design phases proceeded in a relatively timely manner for the first half of the project. However, during latter stages of manufacture and fuel cell testing, a variety of issues were encountered that ultimately resulted in several delivery delays, and a number of contract modifications. Final installation and field testing was completed in April and May 2003. Final acceptance of the fuel cell was completed on May 16, 2003. The fuel cell has operated successfully for more than one year. The unit achieved an availability rate of 96%, which exceeded expectations. The capacity factor was limited because the unit was set at 155 kW (versus a nameplate of 250 kW) due to the interconnection with the electric utility. There were 18 shutdowns during the first year and most were brief. The ability of this plant to operate in the island mode improved availability by 3 to 4%. Events that would normally be shutdowns were simply island mode events. The mean time between failure was calculated at 239 hours, or slightly less than 10 days. The fuel cell did run continuously for more than one month on three occasions during the first year. Overall efficiency, including the thermal recovery, was found to be over 60%. Operation for the fuel cell during the first year produced net savings for the Coast Guard of over $18,000.« less