Technologies for measuring flow rates of outdoor air into HVACsystems: Some causes and suggested cures for measurement errors
Journal Article
·
· ASHRAE Transactions
OSTI ID:881724
Although the rate of outdoor air (OA) ventilation has a substantial influence on building energy consumption and occupant health, the available data indicate the outdoor air ventilation rates are poorly controlled in many buildings. Technologies being marketed for real time measurement of the flow rates of outdoor air into HVAC systems should enable better control of OA ventilation. In laboratory research they have studied the performance of these technologies. Sources of measurement errors identified during conduct of this research include: low air speeds; high spatial variability in air speed and direction; large eddies downstream of outdoor air intake louvers; and backwards airflow through a portion of outdoor air dampers. Several suggestions for overcoming these sources of errors were developed including: design and control of the outdoor air intake system to avoid low, hard-to measure, air speeds; use of highly sensitive pressure and velocity sensors; measuring air speeds between blades of louvers, rather than downstream of louvers; smoothing out the airflow between the outdoor air louver and damper through proper louver selection and insertion of components to straighten air flow; and maintaining a pressure drop across the outdoor air damper that exceeds approximately 0.04 IWG (10 Pa).
- Research Organization:
- Ernest Orlando Lawrence Berkeley NationalLaboratory, Berkeley, CA (US)
- Sponsoring Organization:
- USDOE. Assistant Secretary for Energy Efficiency andRenewable Energy. Office of the Building Technologies Program
- DOE Contract Number:
- AC02-05CH11231
- OSTI ID:
- 881724
- Report Number(s):
- LBNL--56604; BnR: BT0201000
- Journal Information:
- ASHRAE Transactions, Journal Name: ASHRAE Transactions Journal Issue: pt2 Vol. 111; ISSN 0001-2505; ISSN ASHTAG
- Country of Publication:
- United States
- Language:
- English
Similar Records
Measuring Outdoor Air Intake Rates into Existing Building
Measuring OutdoorAir Intake Rates Using Electronic Velocity Sensors at Louvers and Downstream of Airflow Straighteners
Measuring Outdoor Airflow into HVAC Systems
Technical Report
·
Thu Apr 16 00:00:00 EDT 2009
·
OSTI ID:994011
Measuring OutdoorAir Intake Rates Using Electronic Velocity Sensors at Louvers and Downstream of Airflow Straighteners
Technical Report
·
Wed Oct 01 00:00:00 EDT 2008
·
OSTI ID:944427
Measuring Outdoor Airflow into HVAC Systems
Journal Article
·
Mon Aug 01 00:00:00 EDT 2005
· ASHRAE Journal
·
OSTI ID:908463