Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Water treatment for open recirculating cooling systems using molybdate/phosphate blends

Book ·
OSTI ID:82974
 [1];  [2]
  1. Rice Univ., Houston, TX (United States). Dept. of Environmental Science and Engineering
  2. Cortest Columbus Technologies, OH (United States)

Laboratory and field tests were undertaken to optimize the ratio of the components and the treatment level of a new inhibitor blend based on molybdate and inorganic phosphate. Laboratory results obtained established the efficiency of this treatment under simulated cooling system operating conditions. In the 90 day field test, the corrosion rate of the steel was found to reduce by 85% with remarkable improvement in the quality of the cooling water.

OSTI ID:
82974
Report Number(s):
CONF-940222--
Country of Publication:
United States
Language:
English