ALS control system IP I/O module upgrade
The Control System for the Advanced Light Source uses in-house designed IndustryPack (IP) I/O Modules in compact PCI (cPCI) chassis to control instrumentation. Each module consists of digital I/O ports and 16-bit analog I/O interfaced to instrumentation via a cPCI rear I/O card. During the past few years of installed operation, several factors have prompted investigation into the design of a new IP I/O Module. The ADC channels have significant offset drift over periods of days of initial installed operation. An in-situ calibration procedure was developed to address this problem, but it lacks speed and is inconvenient to perform. Digital I/O port limitations have led to increasing amounts of wasted I/O. Fast orbit feedback requires faster ADC sampling and better filtering than the current IP module offers. This paper discusses the issues related to the current IP I/O Module and the design of a new Double-size IP I/O Module.