Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

LABORATORY EVALUATION OF THE DELTA Q TEST FOR DUCT LEAKAGE

Technical Report ·
DOI:https://doi.org/10.2172/811286· OSTI ID:811286
 [1]
  1. BROOKHAVEN NATIONAL LABORATORY
Using a residential-size duct system in a controlled laboratory setting, the repeatability and accuracy of the Delta Q test for air leakage in residential duct systems have been measured. More than 100 Delta Q tests were performed. These were compared with results using fan pressurization and also with results of a procedure (Delta Q Plus) that uses leakage hole-size information to select the leakage pressures to be used in the Delta Q algorithm. The average error in supply or return leakage for the fan-pressurization test was 6.4% of system fan flow. For the Delta Q test it was 3.4% of fan flow, while for Delta Q Plus it was 1.9% of fan flow.
Research Organization:
Brookhaven National Lab., Upton, NY (US)
Sponsoring Organization:
DOE/SC (US)
DOE Contract Number:
AC02-98CH10886
OSTI ID:
811286
Report Number(s):
BNL--71220-2003-IR; EC0904000
Country of Publication:
United States
Language:
English