Comparison between predicted duct effectiveness from proposed ASHRAE Standard 152P and measured field data for residential forced air cooling systems
- LBNL Library
The proposed ASHRAE Standard 152P ''Method of Test for Determining the Design and Seasonal Efficiencies of Residential Thermal Distribution Systems'' (ASHRAE 2002) has recently completed its second public review. As part of the standard development process, this study compares the forced air distribution system ratings provided by the public review draft of Standard 152P to measured field results. 58 field tests were performed on cooling systems in 11 homes in the summers of 1998 and 1999. Seven of these houses had standard attics with insulation on the attic floor and a well-vented attic space. The other four houses had unvented attics where the insulation is placed directly under the roof deck and the attic space is not deliberately vented. Each house was tested under a range of summer weather conditions at each particular site, and in some cases the amount of duct leakage was intentionally varied. The comparison between 152P predicted efficiencies and the measured results includes evaluation of the effects of weather, duct location, thermal conditions, duct leakage, and system capacity. The results showed that the difference between measured delivery effectiveness and that calculated using proposed Standard 152P is about 5 percentage points if weather data, duct leakage and air handler flow are well known. However, the accuracy of the standard is strongly dependent on having good measurements of duct leakage and system airflow. Given that the uncertainty in the measured delivery effectiveness is typically also about 5 percentage points, the Standard 152P results are acceptably close to the measured data.
- Research Organization:
- Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US)
- Sponsoring Organization:
- USDOE Assistant Secretary for Energy Efficiency and Renewable Energy. Office of Building Technology, State and Community Programs. Office of Building Research and Standards; California Institute for Energy Efficiency (US)
- DOE Contract Number:
- AC03-76SF00098
- OSTI ID:
- 795371
- Report Number(s):
- LBNL--50008
- Country of Publication:
- United States
- Language:
- English
Similar Records
Verification test of ASHRAE Standard 152P
Reproducibility of ASHRAE Standard 152P: Results of a round-robin test
Error analysis for duct leakage tests in ASHRAE standard 152P
Conference
·
Thu Oct 01 00:00:00 EDT 1998
·
OSTI ID:649464
Reproducibility of ASHRAE Standard 152P: Results of a round-robin test
Conference
·
Thu Oct 01 00:00:00 EDT 1998
·
OSTI ID:649462
Error analysis for duct leakage tests in ASHRAE standard 152P
Technical Report
·
Sun Jun 01 00:00:00 EDT 1997
·
OSTI ID:534521