Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Energy and indoor environmental quality in relocatable classrooms

Conference ·
OSTI ID:792976

Relocatable classrooms (RCs) are commonly utilized by school districts with changing demographics and enrollment sizes. Four energy-efficient RCs were designed and constructed for this study to demonstrate technologies that simultaneously attempt to improve energy efficiency and indoor environmental quality (IEQ). Two were installed at each of two school districts, and energy use and IEQ parameters were monitored during occupancy. Two (one per school) were finished with materials selected for reduced emissions of toxic and odorous volatile organic compounds (VOCs). Each RC had two HVAC systems, alternated weekly, consisting of a standard heat-pump system and an indirect-direct evaporative cooling (IDEC) system with gas-fired hydronic heating. The hypothesized advantages of the IDEC include continuous outside air ventilation at {ge}7.5 L s{sup -1} per person, {approx}70% less cooling energy and efficient particle filtration. Measurements include: carbon dioxide, particles, VOCs, temperature, humidity, thermal comfort, noise, meteorology, and energy use. Preliminary IEQ monitoring results are reported.

Research Organization:
Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US)
Sponsoring Organization:
USDOE Assistant Secretary for Energy Efficiency and Renewable Energy (US)
DOE Contract Number:
AC03-76SF00098
OSTI ID:
792976
Report Number(s):
LBNL--49581
Country of Publication:
United States
Language:
English