Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Transient response of a shell and tube heat exchanger

Conference ·
OSTI ID:78292
 [1]
  1. Public Service Electric and Gas Co., Hancocks Bridge, NJ (United States)

Governing partial differential equations describing transient heat transfer for a one shell pass and two tube pass heat exchanger have been derived. These equations were solved using a finite difference method. The ultimate steady state temperatures agree well with the available closed form solution. The transient response of a heat exchanger can be used to predict its overall fouling resistance when steady state testing becomes impractical due to lack of sufficient heat load.

OSTI ID:
78292
Report Number(s):
CONF-941007--; ISBN 0-7918-1385-1
Country of Publication:
United States
Language:
English

Similar Records

Application of a stepwise method for analyzing fouling in shell-and-tube exchangers
Journal Article · Tue Nov 30 23:00:00 EST 1999 · Heat Transfer Engineering · OSTI ID:20006029

Effectively design shell-and-tube heat exchangers
Journal Article · Sat Jan 31 23:00:00 EST 1998 · Chemical Engineering Progress · OSTI ID:605699

Influence of scaling on the performance of shell-and-tube heat exchangers