skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Dedication of emergency diesel generators` control air subsystem

Journal Article · · Transactions of the American Nuclear Society
OSTI ID:76057

In the spring of 1993, the need to upgrade Seabrook Station`s emergency diesel generators` (EDGs`) control air system from nonsafety related to safety related was identified. This need was identified as a result of questions raised by the US Nuclear Regulatory Commission, which was conducting an Electrical Distribution Safety Functional Inspection at Seabrook at that time. The specific reason for the reassignment of safety classification was recognition that failure of the control air supply to the EDGs` jacket cooling water temperature control valves could cause overcooling of the EDGs, which potentially could result in EDG failure during long-term operation. This paper addresses how the installed control air system was upgraded to safety related using Seabrook`s Commercial Grade Dedication (CGD) Program and how, by using the dedication skills obtained over the past few years, it was done at minimal cost.

OSTI ID:
76057
Report Number(s):
CONF-940602-; ISSN 0003-018X; TRN: 95:003867-0234
Journal Information:
Transactions of the American Nuclear Society, Vol. 70; Conference: 35. annual meeting of the American Nuclear Society, New Orleans, LA (United States), 11-16 Jun 1994; Other Information: PBD: 1994
Country of Publication:
United States
Language:
English