ASSESSMENT OF CABLE AGING USING CONDITION MONITORING TECHNIQUES
Conference
·
OSTI ID:759037
- BROOKHAVEN NATIONAL LABORATORY
Electric cables in nuclear power plants suffer degradation during service as a result of the thermal and radiation environments in which they are installed. Instrumentation and control cables are one type of cable that provide an important role in reactor safety. Should the polymeric cable insulation material become embrittled and cracked during service, or during a loss-of-coolant-accident (LOCA) and when steam and high radiation conditions are anticipated, failure could occur and prevent the cables from fulfilling their intended safety function(s). A research program is being conducted at Brookhaven National Laboratory to evaluate condition monitoring (CM) techniques for estimating the amount of cable degradation experienced during in-plant service. The objectives of this program are to assess the ability of the cables to perform under a simulated LOCA without losing their ability to function effectively, and to identify CM techniques which may be used to determine the effective lifetime of cables. The cable insulation materials tested include ethylene propylene rubber (EPR) and cross-linked polyethylene (XLPE). Accelerated aging (thermal and radiation) to the equivalent of 40 years of service was performed, followed by exposure to simulated LOCA conditions. The effectiveness of chemical, electrical, and mechanical condition monitoring techniques are being evaluated. Results indicate that several of these methods can detect changes in material parameters with increasing age. However, each has its limitations, and a combination of methods may provide an effective means for trending cable degradation in order to assess the remaining life of cables.
- Research Organization:
- Brookhaven National Lab., Upton, NY (US)
- Sponsoring Organization:
- U.S. NUCLEAR REGULATORY COMMISSION (US)
- DOE Contract Number:
- AC02-98CH10886
- OSTI ID:
- 759037
- Report Number(s):
- BNL--NUREG-67345; 401001060; 401001060
- Country of Publication:
- United States
- Language:
- English
Similar Records
Long-term aging and loss-of-coolant accident (LOCA) testing of electrical cables
Assessment of Environmental Qualification Practices and Condition Monitoring Techniques for Low-Voltage Electric Cables: LOCA Test Results
Application of Cable Condition Monitoring Technologies to Assess Age-Related Degradation of Industrial Cables Installed in Harsh Environments
Technical Report
·
Tue Oct 01 00:00:00 EDT 1996
·
OSTI ID:385579
Assessment of Environmental Qualification Practices and Condition Monitoring Techniques for Low-Voltage Electric Cables: LOCA Test Results
Technical Report
·
Wed Jan 31 23:00:00 EST 2001
·
OSTI ID:1329393
Application of Cable Condition Monitoring Technologies to Assess Age-Related Degradation of Industrial Cables Installed in Harsh Environments
Journal Article
·
Fri Apr 02 20:00:00 EDT 2021
· Nuclear Technology
·
OSTI ID:1878288