Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Technology development: HEPA filter service life test plan

Technical Report ·
DOI:https://doi.org/10.2172/73030· OSTI ID:73030

Rocky Flats Environmental Technology Site (the Site) has approximately 10,000 High Efficiency Particulate Air (HEPA) Filters installed in a variety of filter plenums. These ventilation/filtration plenum systems are used to control the release of airborne particulate contaminates to the environment during normal operations and also during potential design-based accidents. The operational integrity of the HEPA filter plenums is essential to maintaining the margins of safety as required by building specific Final Safety Analysis Reports (FSARS) for protection of the public and environment. An Unreviewed Safety Question Determination (USQD), USDQ-RFP94.0615-ARS, was conducted in 1994 addressing the potential inadequacy of the safety envelope for Protected Area building HEPA plenums. While conducting this USQD, questions were raised concerning the maximum service life criteria for HEPA filters. Accident scenarios in existing FSARs identify conditions that could potentially cause plugging or damage of down stream HEPA filters as a result of impaction from failed filters. Additionally, available data indicates that HEPA filters experience structural degradation due to the effects of age. The Unresolved Safety Question (USQ) compensatory measures thus require testing and analysis of used HEPA filters in order to determine and implement service life criteria.

Research Organization:
Rocky Flats Environmental Technology Site, Golden, CO (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC34-90RF62349
OSTI ID:
73030
Report Number(s):
RFP--4954; ON: DE95013235
Country of Publication:
United States
Language:
English

Similar Records

Evaluation of HEPA filter service life
Technical Report · Mon Jul 14 00:00:00 EDT 1997 · OSTI ID:519156

Closure of 324 Facility potential HEPA filter failure unreviewed safety questions
Technical Report · Thu Nov 06 23:00:00 EST 1997 · OSTI ID:362358

Plutonium Finishing Plant (PFP) Waste Composition and High Efficiency Particulate Air Filter Loading