Investigation and status report on concentric neutral corrosion of URD extruded cable. Final report
The use of cables with extruded insulation and concentric neutral wires has been widely accepted for underground distribution in recent years and substantial continued use of this cable is anticipated. Recent reports of incidences of corrosion of the neutral strands have produced concern about problems which may result. The integrity of the neutral wires is important because it provides a low impedance both for load and short circuit currents and maintains acceptable voltage levels to equipment and personnel during short circuit conditions. A compilation of the information obtained from a literature search and a field investigation is presented. Results obtained in corrosion surveys of underground residential distribution (URD) cables are also included. The study concentrated on ascertaining present opinions about the cause or causes of concentric neutral corrosion and on determining present industry practice in corrosion mitigation. This investigation found no general agreement about the cause of concentric neutral corrosion and indeed there was even disagreement about the extent and seriousness of the problem. It is concluded that the neutral corrosion results from either stray dc currents or natural galvanic action and that ac is not an important factor. Present mitigation practice focuses mostly on jacketing and cathodic protection. There is a need for additional work in determining the effectiveness of these practices and in prescribing procedures for their use.
- Research Organization:
- Harco Corp., Medina, OH (USA)
- OSTI ID:
- 7294522
- Report Number(s):
- EPRI-EL-362
- Country of Publication:
- United States
- Language:
- English
Similar Records
Jacketed URD cable advantages unearthed at FP and L, Georgia Power
Computer program for determination of earth potentials due to faults or loss of concentric neutral on URD cable. [BACB Code]
Corrosion of the concentric neutrals of buried URD cables. Final report
Journal Article
·
Fri Feb 29 23:00:00 EST 1980
· Electr. Light Power (Boston); (United States)
·
OSTI ID:5426285
Computer program for determination of earth potentials due to faults or loss of concentric neutral on URD cable. [BACB Code]
Technical Report
·
Sun May 01 00:00:00 EDT 1977
·
OSTI ID:7212946
Corrosion of the concentric neutrals of buried URD cables. Final report
Technical Report
·
Wed May 01 00:00:00 EDT 1985
·
OSTI ID:5322558
Related Subjects
200301* -- Power Transmission & Distribution-- AC Systems
EHV & UHV-- (-1989)
24 POWER TRANSMISSION AND DISTRIBUTION
AC SYSTEMS
CABLES
CHEMICAL REACTIONS
CONDUCTOR DEVICES
COPPER
CORROSION
CORROSION PROTECTION
DATA
ELECTRIC CABLES
ELECTRICAL EQUIPMENT
ELECTRICAL INSULATION
ELEMENTS
EQUIPMENT
INFORMATION
METALS
POWER SYSTEMS
POWER TRANSMISSION
POWER TRANSMISSION LINES
TRANSITION ELEMENTS
UNDERGROUND POWER TRANSMISSION
EHV & UHV-- (-1989)
24 POWER TRANSMISSION AND DISTRIBUTION
AC SYSTEMS
CABLES
CHEMICAL REACTIONS
CONDUCTOR DEVICES
COPPER
CORROSION
CORROSION PROTECTION
DATA
ELECTRIC CABLES
ELECTRICAL EQUIPMENT
ELECTRICAL INSULATION
ELEMENTS
EQUIPMENT
INFORMATION
METALS
POWER SYSTEMS
POWER TRANSMISSION
POWER TRANSMISSION LINES
TRANSITION ELEMENTS
UNDERGROUND POWER TRANSMISSION