The Oklahoma Field Test: Air-conditioning electricity savings from standard energy conservation measures, radiant barriers, and high-efficiency window air conditioners
A field test Involving 104 houses was performed in Tulsa, Oklahoma, to measure the air-conditioning electricity consumption of low-income houses equipped with window air conditioners, the reduction in this electricity consumption attributed to the installation of energy conservation measures (ECMS) as typically installed under the Oklahoma Weatherization Assistance Program (WAP), and the reduction achieved by the replacement of low-efficiency window air conditioners with high-efficiency units and the installation of attic radiant barriers. Air-conditioning electricity consumption and indoor temperature were monitored weekly during the pre-weatherization period (June to September 1988) and post-weatherization period (May to September 1989). House energy consumption models and regression analyses were used to normalize the air-conditioning electricity savings to average outdoor temperature conditions and the pre-weatherization indoor temperature of each house. The following conclusions were drawn from the study: (1) programs directed at reducing air-conditioning electricity consumption should be targeted at clients with high consumption to improve cost effectiveness; (2) replacing low-efficiency air conditioners with high-efficiency units should be considered an option in a weatherization program directed at reducing air-conditioning electricity consumption; (3) ECMs currently being installed under the Oklahoma WAP (chosen based on effectiveness at reducing space-heating energy consumption) should continue to be justified based on their space-heating energy savings potential only; and (4) attic radiant barriers should not be included in the Oklahoma WAP if alternatives with verified savings are available or until further testing demonstrates energy savings or other benefits in this typo of housing.
- Research Organization:
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE; USDOE, Washington, DC (United States)
- DOE Contract Number:
- AC05-84OR21400
- OSTI ID:
- 7167800
- Report Number(s):
- ORNL/CON-317; ON: DE93003668
- Country of Publication:
- United States
- Language:
- English
Similar Records
The Oklahoma Field Test: Air-Conditioning Electricity Savings from Standard Energy Conservation Measures, Radiant Barriers, and High-Efficiency Window Air Conditioners
Measured space-cooling electricity savings from standard energy conservation measures, radiant barriers, and high-efficiency window air conditioners
Related Subjects
AIR CONDITIONERS
FIELD TESTS
HOUSES
ENERGY CONSUMPTION
AIR CONDITIONING
EFFICIENCY
ELECTRICITY
ENERGY CONSERVATION
OKLAHOMA
TEMPERATURE MEASUREMENT
BUILDINGS
DEVELOPED COUNTRIES
FEDERAL REGION VI
NORTH AMERICA
RESIDENTIAL BUILDINGS
TESTING
USA
320105* - Energy Conservation
Consumption
& Utilization- Building Services- (1987-)
320106 - Energy Conservation
Consumption
& Utilization- Building Equipment- (1987-)